Application: Analog fault signalling (2-state output)

In 2-state mode, the loop current signals whether the probe is covered or uncovered, and the continuous level measurement is unavailable.

2-state mode provides:

a 4 mA or 20 mA output to menu 07, when the level reaches one of the threshold settings

a 3.6 or 22 mA output to menu 07 (if 2-state fault signalling is enabled at menu 08) when the process level exceeds one of the limit settings (menu 0B and 0C).

The above settings can be modified:

The response time when thresholds are reached can be modified by Upper and/ or Lower Threshold delays (menus 03 and 04).

The mA reading can be stabilized if necessary by applying Damping (menu 0A): the increment value is controlled at menu 09.

Example:

Current activated relay module

current loop connection

Active Shield section

(menu 0C) USL (menu 0F) URV = 100%

Upper Threshold Level = 90% menu 05 (activation hysteresis)

2-state output (menu 07)

menu 06 (deactivation hysteresis) Lower Threshold Level = 8% Menu 0E LRV = 0% Menu 0B LSL

P

83.5pF 75.8 pF

14.3pF

7.3pF

Appendix E

Device settings:

 

 

(The device is first restored to factory settings before being commissioned)

 

TV0 selected: Transmitter Variable 0 is PV

Menu 01 reads

Pv = 0

Lower Range Value (0% of range) is set to 14.3

Menu 0E reads

14.30

Upper Range Value (100% of range) is set to 75.8

Menu 0F reads

75.80

Current loop is in 2-state mode (C: Hi selected)

Menu 07 reads

C:Hi

2-state fault signalling enabled (F: Hi selected

Menu 08 reads

F:Hi1

Activation hysteresis is set to 90

Menu 05 reads

90.0

Deactivation hysteresis is set to 8

Menu 16 reads

08.0.

1.F: Hi appears while the button is pressed. See Analog Fault Signalling (2-state)on page 66 for more details.

Page 94

SITRANS LC 500 – INSTRUCTION MANUAL

7ML19985GE01