Start Up
Menu levels 0 and 1
Menu level 00 to 0F is the default
To change from menu 00 to menu 10:
1.Set the rotary switch to 0.
2.Press and hold the BLUE
3.While the button is pressed, the display shows : M 10 followed by : SEL 1,
indicating that the current menu level is now 10 to 1F: a
4.When the button is released, the LCD displays PV (primary variable): the left- arrow remains visible.
To change from menu 10 to menu 00:
1.Make sure the rotary switch is set to 0.
2.Press and hold the RED (+) button.
3.While the button is pressed, the display shows: M 00 followed by : SEL 0,
indicating that the current menu level is 00 to 0F: no
4.When the button is released, the LCD displays PV.
In menu 00 or 10, to see the current menu level selection, briefly press one of the buttons (less than a second): the current selection is momentarily displayed.
Notes:
•Check the menu level when using the rotary switch to select a menu item: the left- arrow in the top left corner of the LCD indicates menu level 1.
•The rotary switch must be set to 0, in order to change from one menu to the other.
•Hold the RED (+) or
•Keylock level (menu 1F) must be set to 0 (no restrictions) to enable you to change settings.
Start up using push-button calibration: (overview)
•Check that Keylock level is set to enable calibration
•If required, change the transmitter variable: select units as pF, units
•Calibrate value for 0%
•Calibrate value for 100%
•Set display for dynamic PV (primary variable): select values displayed as percent or units
•SITRANS LC 500 is ready to operate
Page 42 | SITRANS LC 500 – INSTRUCTION MANUAL | 7ML19985GE01 |