Certificates and Approvals

The Intrinsic Safety Specifications of the SITRANS LC 500 have been defined and approved as follows:

Application

Specifications

 

 

current loop insulated from the measuring circuit

3.6-22 mA

internal capacitance

can be ignored

internal inductance

10 µH

maximum supply voltage

30 Vdc

maximum current

200 mA

maximum power consumption

1.5 W

The SITRANS LC 500 can be directly connected to an intrinsically safe supply for intrinsically safe applications. For non-intrinsically safe operations, such as explosion proof, a safety barrier must be used.

The operation of the SITRANS LC 500 conforms to the following:

NAMUR recommendation NE 43

This recommendation describes rules by which analog transmitters transfer their information to DCS equipment. This information can be divided into two types:

measurement information

For measurement information the current signal should be within the range of 3.8 to 20.5 mA.

failure signalling

For failure information which indicates a failure in the measuring system1 the current signal should be in the range of either 0 to 3.6 mA, or 21 mA or greater.

The application will determine which of these two ranges is more desirable. The SITRANS LC 500 can be set for 3.6 mA, or 22 mA, as required2.

Appendix F

1.It may also signal a process level outside the Upper and Lower Sensor Limits, if the unit has been programmed for this. For more information, see Fault Signalling on page 15.

2.See Analog Fault Signalling (2-state) on page 66 for details.

7ML19985GE01

SITRANS LC 500 – INSTRUCTION MANUAL