Siemens Sitrans Menu Items, Transmitter Variable Settings menu level, Appendix A, Affected

Models: Sitrans

1 122
Download 122 pages 51.76 Kb
Page 61
Image 61
Menu Items

Menu Items

Notes:

Check that you are at the correct menu level before selecting a menu item.

Hold the RED or BLUE buttons for longer than the preset delay, or debounce time to change a setting: this debounce time is generally around a second, but varies from one menu item to another.

Protection is set at keylock level, menu 1F: make sure the setting is appropriate.

The transmitter variable, units as pF, units user-defined, or values as percent, is set at menu 01; make sure the setting is appropriate.

Reset to factory settings at menu 12: factory settings are indicated with an asterisk in the tables, unless explicitly described.

Transmitter: Variable Settings: menu level 0

Notes:

You must select menu level 0 before you can access the items at that level.

The transmitter variable must be set for units in pF to enable settings to be changed by push-button adjustment: (menu 01 must be set to PV = 0).

Stepsize Update Value

This menu selection controls the increment/decrement step-size for the menus 0B, 0C, 0D, 0E, 0F, and 03.

Menu

Affected

Rotary

Left

 

 

Switch

Description

Values

Item

by:

Position

Arrow

 

 

09

01

9

Off

Stepsize Update Value

Range: 0.01 to 1000

 

 

Factory setting

U: 1.0

 

 

 

 

 

 

 

 

 

 

1.Set the rotary switch to 9.

2.Press the RED (+) or BLUE (–) button to increase or decrease this value in decades: you can step the value up to 10, 100, and 1000 (1E3), or down to 0.1 and 0.01.

3.Press and hold both buttons simultaneously to restore the value to U:1.0

Appendix A

7ML19985GE01

SITRANS LC 500 – INSTRUCTION MANUAL

Page 55

Page 61
Image 61
Siemens Sitrans, LC 500 instruction manual Menu Items, Transmitter Variable Settings menu level, Appendix A, Affected