Appendix A

(SIM) function has been selected via HART, the LCD alternately displays the text SIM or the applied simulation value for the duration of the simulation.

Menu

Affected

Rotary

Left

Description

Values

Item

by:

Switch

Arrow

 

 

Position

 

 

 

00

01

0

Off

Dynamic Value (PV)

Units or % of range, selected

 

 

in menu 01

10

On

 

 

 

 

 

 

 

 

 

To change from menu 10 to menu 00:

1.Set the rotary switch to 0.

2.Press the RED (+) button for about a second. The LCD briefly displays : M 00

followed by : SEL 0, to indicate that menu 00 is selected. When the button is released the LCD displays the current PV value. No left-arrow is displayed at the top left corner of the LCD in menu 00.

To change from menu 00 to menu 10:

1.Set the rotary switch to 0.

2.Press the BLUE button for more than one second. The LCD briefly displays : M 10

followed by : SEL1, to indicate that menu level 1 is selected. Then the LCD displays PV, and a left-arrow is visible in the top left corner of the LCD, indicating menu level 1.

Display the Highest / Lowest Recorded Value

Menu

Rotary

 

 

Switch

Left Arrow

Description

Item

Position

 

 

 

 

 

02

2

Off

Highest / Lowest Recorded Value

 

 

 

 

1.Set the rotary switch to 2. The Highest / Lowest recorded values for TV currently selected are displayed alternately.

2.Press the RED (+) button to select the Highest recorded value for display,

or: Press the BLUE (–) button to select the Lowest recorded value for display,

3.Press both buttons simultaneously for more than one second to reset the recorded values back to the dynamic value of this TV. (This will also occur after a reset [power-down] of the device.)

Select the Transmitter Variable (TV) for the Primary Variable (PV).

Menu

Rotary

Left

 

 

 

 

Switch

Description

Values

Item

Position

Arrow

 

 

 

 

 

 

 

 

0

*

TVO (units are pF)

 

 

 

Transmitter Variable

 

 

 

01

1

Off

1

 

TV1 (units are user definable

 

 

 

selection for PV

 

 

only via HART)

 

 

 

 

P

 

TV0 (values displayed as %)

 

 

 

 

 

 

 

Page 60

SITRANS LC 500 – INSTRUCTION MANUAL

7ML19985GE01

Page 66
Image 66
Siemens LC 500, Sitrans Rotary Left Description Values Switch, Display the Highest / Lowest Recorded Value, Arrow