Siemens Sitrans, LC 500 instruction manual Appendix A, Menu, Affected, Left Arrow, 3300 to

Models: Sitrans

1 122
Download 122 pages 51.76 Kb
Page 63
Image 63
Left Arrow

Upper Sensor Limit

The Upper Sensor Limit (USL) is the upper of two limit settings. Whenever the PV value (Menu Level 0) rises above the upper limit setting, the measurement is considered at fault and the LCD displays ooL, alternating with PV.

If the display mode is in %, this selection is disabled and the LCD displays - - - -. The transmitter variable on which this menu selection operates is chosen in Menu 01.

The increment/decrement step size is subject to the setting from Menu 09.

Menu

Affected

Rotary

 

 

 

Switch

Left Arrow

Description

Values

Item

by:

Position

 

 

 

 

 

 

 

 

0C

01, 09

C

Off

Upper Sensor Limit

3300 to 0

 

 

Factory setting

3300

 

 

 

 

 

 

 

 

 

 

1.Set the rotary switch to C.

2.Press the RED (+) or BLUE (–) button to increase or decrease this value. or: Press and hold a button to start a repeat function.

or: Press and hold both buttons simultaneously to take the current PV reading as the new setting.

Delta Range Setting

The Delta Range Setting allows you to commission the unit for overfill or underfill protection where it is impossible to bring the product to those levels in normal process conditions. This feature is not normally used for the SITRANS LC 500.

Overfill protection is used in applications where the probe is normally uncovered. Delta Range Setting adds the minimum span to the Lower Range Value: the result is used to update the Upper Range Value. If the process level exceeds the new URV, a fault is signalled.

Underfill protection would be used in applications where the probe is normally covered. In this case, Delta Range Setting subtracts the minimum span from the Upper Range Value and uses the result to update the Lower Range Value. If the process value drops below the new LRV, a fault is signalled.

The loop-current control must be in 2-state mode (Menu 07) for Menu 0D to display the Delta Range Setting. When the loop-current control is in Analog mode, Menu 0D displays - - - -.

Appendix A

7ML19985GE01

SITRANS LC 500 – INSTRUCTION MANUAL

Page 57