Safety

current signalling according to NAMUR NE 43;

 

 

3.6 to 22 mA / 22 to 3.6 mA

 

probe input ESD protected to 55 kV

 

inputs/outputs fully galvanically isolated

 

polarity-insensitive current loop

 

fully potted

 

integrated safety barrier

Diagnostics (Includes

primary variable (PV) out of limits

fault alarm)

system failure measurement circuit

 

deviation between A/D and D/A converter

 

 

values

 

check sum

 

watch dog

 

self-checking facility

Outputs

galvanically isolated

 

damping

range 1 to 10,000

Current loop

 

continuous signal

4 to 20 mA / 20 to 4 mA

2-state functionality

4 or 20 mA / 20 or 4 mA, on or off

time delay

1 to 100 sec. activating / de-activating

• adjustable hysteresis (on / off)

0 to 100%, min. 1% of range

Solid-state switch

40 Vdc / 28 Vac / 100 mA at 2 VA max.

time delay

1 to 100 sec. activating / de-activating

• adjustable hysteresis (on / off)

0 to 100%, min. 1% of range

User Interface

Local digital display

4 1/2 digit LCD

Rotary function switch

for selecting programmable menu items

• 16 Positions

0 to 9, A to F

Push-buttons: RED (+), BLUE (–)

used in conjunction with rotary switch, for

 

programming menu items

Communications

HART 1 Communication protocol

Specifications

1.HART® is a registered trademark of the HART Communications Foundation.

7ML19985GE01

SITRANS LC 500 – INSTRUCTION MANUAL

Page 5

Page 11
Image 11