FORM
The default values shown below are entered into memory, when the program option is selected. The list also provides the low and high limits the micro will accept.
Program Value | Mode | Low Limit | High Limit | Default | |
Display Language | NA | NA | English | ||
Discharge Pressure Cutout | 200 PSIG | 399 PSIG | 399 PSIG | ||
13.8 Bars | 27.5 Bars | 27.5 Bars | |||
|
| ||||
Discharge Pressure Unload | 200 PSIG | 399 PSIG | 375 PSIG | ||
13.8 Bars | 27.5 Bars | 25.9 Bars | |||
|
| ||||
| Water Cooling | 44.0 PSIG | 70.0 PSIG | 44.0 PSIG | |
Suction Pressure Cutout | 3.03 Bars | 4.83 Bars | 30.3 Bars | ||
| |||||
Glycol Cooling | 5.0 PSIG | 70.0 PSIG | 44.0 PSIG | ||
| |||||
| 0.34 Bars | 4.83 Bars | 3.03 Bars | ||
|
| ||||
High Ambient Air Temp Cutout | 100.0 ºF | 130.0 ºF | 130.0 ºF | ||
37.8 ºC | 54.4 ºC | 54.4 ºC | |||
|
| ||||
| Standard | 25.0 ºF | |||
Low Ambient Ait Temperature Cutout | Ambient | ||||
Low | 0 ºF | 50.0 ºF | 25.0 ºF | ||
| |||||
| Ambient | 10.0 ºC | |||
| Water Cooling | 36.0 | |||
| 2.2 | ||||
|
| ||||
Leaving Chilled Liquid Temp Cutout | Glycol Cooling | 8.0 ºF | 36.0 ºF | 36.0 ºF | |
2.2 ºC | 2.2 ºC | ||||
|
| ||||
| Low Temp Glycol | 36.0 ºF | 36.0 ºF | ||
|
| 2.2 ºC | 2.2 ºC | ||
High Motor Current Unload | 30% | 105% | 100 | ||
Anti Recycle Time | 300 sec | 600 sec | 600 sec | ||
Local / Remote Mode | NA | NA | Local | ||
Units Mode | NA | NA | Imperial | ||
Lead / Lag Control Mode | NA | NA | Automatic | ||
Power Failure Restart Mode | NA | NA | Automatic | ||
Motor Current Averaging Cutout | 30% FLA | 110% FLa | 70 % FLA | ||
Suction Superheat Setpoint | EEV | 9.0 ºF | 15.0 ºF | 12.0 ºF | |
5.0 ºC | 8.3 ºC | 6.6 ºC | |||
|
|
8
YORK INTERNATIONAL | 171 |