Technical Data

FORM 201.19-NM1 (204)

DIMENSIONS – YCAS0200 - YCAS0230 (ENGLISH)

LD03748a

SYS.#1

SYS.#2

MICRO-COMPUTER

CONTROL CENTER

COILS

COILS

 

C

C

 

 

 

OPTIONS PANEL

B

 

B

 

 

18"

1 11/16"

88"

913/8"

VIEW A-A

15/16" (EDGE OF UNIT TO COOLER CONNECTION)

LD03748

NOTES:

1.Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reli- able operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable air flow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high pressure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 6'; rear to wall - 6'; control panel end to wall - 4'; top - no obstructions allowed; distance between adjacent units - 10'. No more than one adjacent wall may be higher than the unit.

FIG. 25 – MODEL YCAS0200 - YCAS0230 DIMENSIONS (ENGLISH)

86

YORK INTERNATIONAL

Page 86
Image 86