Technical Data
FORM
TEMPERATURE AND FLOWS
(SI UNITS)
MODEL | LEAVING WATER | Evaporator FLOW | AIR ON CONDENSER (°C) | ||||
NUMBER | TEMPERATURE (°C) |
| (l/s3) | ||||
|
|
| |||||
YCAS |
|
|
|
|
|
|
|
MIN.1 | MAX.2 | MIN. |
| MAX. | MIN. | MAX | |
0130EC | 4.4 | 12.8 | 8.7 |
| 33.1 | 51.7 | |
0140EC | 4.4 | 12.8 | 8.7 |
| 33.1 | 51.7 | |
0150EC | 4.4 | 12.8 | 12.6 |
| 37.9 | 51.7 | |
0160EC | 4.4 | 12.8 | 12.6 |
| 37.9 | 51.7 | |
0170EC | 4.4 | 12.8 | 12.6 |
| 37.9 | 51.7 | |
0180EC | 4.4 | 12.8 | 12.6 |
| 37.9 | 51.7 | |
0200EC | 4.4 | 12.8 | 15.8 |
| 47.3 | 51.7 | |
0210EC | 4.4 | 12.8 | 15.8 |
| 47.3 | 51.7 | |
0230EC | 4.4 | 12.8 | 15.8 |
| 47.3 | 51.7 |
NOTES:
1.For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK office for application requirements.
2.For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK office for application guidelines.
3.The evaporator is protected against freezing to
Excessive flow, above the max GPM, will damage the evaporator.
50 | YORK INTERNATIONAL |