Technical Data

FORM 201.19-NM1 (204)

TEMPERATURE AND FLOWS

(SI UNITS)

MODEL

LEAVING WATER

Evaporator FLOW

AIR ON CONDENSER (°C)

NUMBER

TEMPERATURE (°C)

 

(l/s3)

 

 

 

YCAS

 

 

 

 

 

 

 

MIN.1

MAX.2

MIN.

 

MAX.

MIN.

MAX

0130EC

4.4

12.8

8.7

 

33.1

-17.7

51.7

0140EC

4.4

12.8

8.7

 

33.1

-17.7

51.7

0150EC

4.4

12.8

12.6

 

37.9

-17.7

51.7

0160EC

4.4

12.8

12.6

 

37.9

-17.7

51.7

0170EC

4.4

12.8

12.6

 

37.9

-17.7

51.7

0180EC

4.4

12.8

12.6

 

37.9

-17.7

51.7

0200EC

4.4

12.8

15.8

 

47.3

-17.7

51.7

0210EC

4.4

12.8

15.8

 

47.3

-17.7

51.7

0230EC

4.4

12.8

15.8

 

47.3

-17.7

51.7

NOTES:

1.For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK office for application requirements.

2.For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK office for application guidelines.

3.The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.

Excessive flow, above the max GPM, will damage the evaporator.

50

YORK INTERNATIONAL

Page 50
Image 50
York YCAS0130 manual Model Leaving Water, AIR on Condenser C, Number Temperature C Ycas