York YCAS0130 manual Temperature And Flows, Technical Data, Si Units

Models: YCAS0130

1 204
Download 204 pages 14.22 Kb
Page 50
Image 50

Technical Data

FORM 201.19-NM1 (204)

TEMPERATURE AND FLOWS

(SI UNITS)

MODEL

LEAVING WATER

Evaporator FLOW

AIR ON CONDENSER (°C)

NUMBER

TEMPERATURE (°C)

 

(l/s3)

 

 

 

YCAS

 

 

 

 

 

 

 

MIN.1

MAX.2

MIN.

 

MAX.

MIN.

MAX

0130EC

4.4

12.8

8.7

 

33.1

-17.7

51.7

0140EC

4.4

12.8

8.7

 

33.1

-17.7

51.7

0150EC

4.4

12.8

12.6

 

37.9

-17.7

51.7

0160EC

4.4

12.8

12.6

 

37.9

-17.7

51.7

0170EC

4.4

12.8

12.6

 

37.9

-17.7

51.7

0180EC

4.4

12.8

12.6

 

37.9

-17.7

51.7

0200EC

4.4

12.8

15.8

 

47.3

-17.7

51.7

0210EC

4.4

12.8

15.8

 

47.3

-17.7

51.7

0230EC

4.4

12.8

15.8

 

47.3

-17.7

51.7

NOTES:

1.For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK office for application requirements.

2.For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK office for application guidelines.

3.The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.

Excessive flow, above the max GPM, will damage the evaporator.

50