York YCAS0130 manual DIMENSIONS - YCAS0200 - YCAS0230 SI, Technical Data

Models: YCAS0130

1 204
Download 204 pages 14.22 Kb
Page 88
Image 88

Technical Data

FORM 201.19-NM1 (204)

All dimensions are in mm unless otherwise noted.

DIMENSIONS – YCAS0200 - YCAS0230 (SI)

LD03751a

VIEW B-B

 

CONTROL ENTRY

 

(8) 22 DIA. HOLES

 

 

SYS.#1

SYS.#2

MICRO-COMPUTER

CONTROL CENTER

COILS

COILS

 

C

C

 

 

 

OPTIONS PANEL

B

 

B

 

 

457

43 2235

2321

VIEW A-A

24 (EDGE OF UNIT TO COOLER CONNECTION)

LD03751

NOTES:

1.Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable air flow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high pressure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; control panel end to wall - 1.2m; top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be higher than the unit.

FIG. 26 – MODEL YCAS0200 - YCAS0230 DIMENSIONS (SI)

88

YORK INTERNATIONAL

Page 88
Image 88
York YCAS0130 manual DIMENSIONS - YCAS0200 - YCAS0230 SI, Technical Data, All dimensions are in mm unless otherwise noted