York YCAS0130 manual Electrical Data, Technical Data, Optional Single-Point Power Supply

Models: YCAS0130

1 204
Download 204 pages 14.22 Kb
Page 60
Image 60

Technical Data

FORM 201.19-NM1 (204)

ELECTRICAL DATA

OPTIONAL SINGLE-POINT POWER SUPPLY

CONNECTION TO FACTORY CIRCUIT BREAKER

Suitable for:

Across-The-Line-Start

One field provided power supply circuit to the unit. Field connections to factory provided Circuit Breaker in the Options Panel. Factory connections to Terminal Blocks in each of the two Power Panels.

See page 62 for notes.

LD05551

OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION TO FACTORY CIRCUIT BREAKER –

2 COMPRESSOR UNITS

(One Field Provided Power Supply Circuit to the chiller. Field Connections to Factory Provided Circuit Breaker.

No Internal Branch Circuit Protection (Breakers) per Motor Control Center10.)

MODEL

VOLTS

 

FIELD SUPPLIED WIRING

 

 

 

SYSTEM #1

 

 

 

 

SYSTEM #2

 

YCAS

MCA1

FACTORY

SUPPLIED BREAKER

COMPRESSOR

 

FANS11,

12

COMPRESSOR

 

FANS11, 12

 

 

 

RATING2

WIRE RANGE7 (LUGS)

RLA

X-LRA

QTY

FLA(ea)

LRA(ea)

RLA X-LRA

QTY

FLA(ea)

 

LRA(ea)

 

 

 

 

0130EC

460

273

400

(2) 3/0-250

107

719

 

4

4.0

19.0

107

719

 

4

4.0

 

19.0

575

217

250

# 6 - 350

86

574

 

4

3.1

15.2

86

574

 

4

3.1

 

15.2

 

 

 

 

0140EC

460

293

400

(2) 3/0-250

116

719

 

4

4.0

19.0

116

719

 

4

4.0

 

19.0

575

234

400

(2) 3/0-250

93

574

 

4

3.1

15.2

93

574

 

4

3.1

 

15.2

 

 

 

 

0150EC

460

307

400

(2) 3/0-250

128

893

 

4

4.0

19.0

115

719

 

4

4.0

 

19.0

575

246

400

(2) 3/0-250

103

714

 

4

3.1

15.2

92

574

 

4

3.1

 

15.2

 

 

 

 

0160EC

460

320

400

(2) 3/0-250

128

893

 

4

4.0

19.0

128

893

 

4

4.0

 

19.0

575

257

400

(2) 3/0-250

103

714

 

4

3.1

15.2

103

714

 

4

3.1

 

15.2

 

 

 

 

0170EC

460

335

400

(2) 3/0-250

140

893

 

4

4.0

19.0

128

893

 

4

4.0

 

19.0

575

268

400

(2) 3/0-250

112

714

 

4

3.1

15.2

103

714

 

4

3.1

 

15.2

 

 

 

 

0180EC

460

347

400

(2) 3/0-250

140

893

 

4

4.0

19.0

140

893

 

4

4.0

 

19.0

575

277

400

(2) 3/0-250

112

714

 

4

3.1

15.2

112

714

 

4

3.1

 

15.2

 

 

 

 

0200EC

460

375

600

(3) 2/0-400

149

893

 

5

4.0

19.0

149

893

 

5

4.0

 

19.0

575

299

400

(2) 3/0-250

119

714

 

5

3.1

15.2

119

714

 

5

3.1

 

15.2

 

 

 

 

0210EC

460

393

600

(3) 2/0-400

163

893

 

5

4.0

19.0

149

893

 

5

4.0

 

19.0

575

313

400

(2) 3/0-250

130

714

 

5

3.1

15.2

119

714

 

5

3.1

 

15.2

 

 

 

 

0230EC

460

407

600

(3) 2/0-400

163

893

 

5

4.0

19.0

163

893

 

5

4.0

 

19.0

575

324

400

(2) 3/0-250

130

714

 

5

3.1

15.2

130

714

 

5

3.1

 

15.2

 

 

 

 

NOTES: Wye-Delta Compressor Start not available with this option.

See page 62 for Electrical Data footnotes.

NOTES:

1.– – – – – – – Dashed Line indicates Field Provided Wiring.

2.The above recommendations are based on the National Electric Code and using copper connectors only. Field wiring must also comply with local codes.

60

YORK INTERNATIONAL

Page 60
Image 60
York YCAS0130 Electrical Data, Technical Data, Optional Single-Point Power Supply, Across-The-Line-Start, Compressor Units