TROUBLESHOOTING GUIDE - CONT’D
PROBLEM | POSSIBLE | ACTION |
SYS # HIGH DSCH | Poor airflow through condenser | Check for airflow restrictions caused by blockages |
displayed (High discharge | coils. | on intake faces of air coils. |
pressure trip) |
| Check for damaged fins/return bends. |
|
| Check for correct fan operation and direction of |
|
| rotation. |
|
| Check for |
| Excessive refrigerant charge. | Check that the |
| Measured pressure is incorrect. | Check discharge transducer and wiring. |
SYS # HIGH DSCH TEMP | Suction superheat too high. | Check suction superheat is within range. |
displayed (High discharge | Poor airflow through the condenser | Check for airflow restrictions caused by blockages |
temperature) | coils. | on intake faces of air coils. |
| Measured temperature incorrect. | Check discharge sensor calibration, location and |
|
| wiring. |
SYS # DSCH LIMITING | Discharge pressure unloading due | Check chilled liquid temperature is within range. |
displayed (Discharge pres- | to unit operating above load limit. | Check fan operation. |
sure unloading) | See also SYS # HIGH DSCH. | Check if ambient air temperature is above design |
|
| conditions. |
|
| Check programmed unload point. |
SYS # HIGH OIL PRESS | Ball valve in oil circuit closed. | Check ball valves are open position. |
DIFF is displyed. (High oil |
|
|
differential pressure.) | Dirty / blocked oil filter. | Check and change oil filter cartridge. |
SYS # LOW SUCTION | Badly adjusted or faulty expansion | Check superheat. |
displayed | valve. |
|
| Reduced evaporator performance. | Check for restricted chilled liquid flow. |
|
| Check for fouled tube surfaces. |
|
| Check superheat. |
| Low refrigerant charge. | Check subcooling is correct. |
|
| Check for leaks. |
| Restricted refrigerant flow. | Check for blocked filter / drier. |
|
| Check LLSV is opening correctly. |
| Measured pressure incorrect. | Check suction pressure transducer and wiring. |
SYS # LOW CURR/MP/HP | Compressor current too low. | Check the compressor main supply voltage, fuses, |
displayed |
| contactors and wiring. Check main supply voltage is |
|
| within tolerance. Check 2ACE MP fault code. |
| Measured current is incorrect. | Check for defective Motor Protector Module. |
| Compressor motor protector signal | Check motor protector and wiring. |
| failure. |
|
| Mechanical high pressure | Check compressor discharge valve is open. |
| trip. | Check |
| No motor cooling. | Check superheat. |
|
| Check operation of economizer, TXV, and liquid |
|
| solenoid valve. |
SYS # CURR LIMITING | High compressor motor current | Check if liquid temperature is within operating limits. |
displayed | has activated unloading. | Check if ambient air temperature is above operating |
(Compressor current un- |
| limits. |
loading.) |
|
|