York YCAS0130 manual Troubleshooting Guide

Models: YCAS0130

1 204
Download 204 pages 14.22 Kb
Page 200
Image 200

Troubleshooting

FORM 201.19-NM1 (204)

TROUBLESHOOTING GUIDE

PROBLEM

 

POSSIBLE CAUSE

ACTION POSSIBLE CAUSE

ACTION

No display on panel -

 

Main supply to control system OFF.

Switch on main supply if safe to do so.

 

unit will not start

 

 

 

Check if control panel emergency stop switch

 

 

Emergency stop device off.

and any remote emergency stop devices are in

 

 

the OFF position. Turn to ON position (1) if safe

 

 

 

 

 

 

 

 

to do so.

 

 

 

CB3 tripped.

Check CB3.

 

 

 

No supply to - T2.

Check 115VAC to L & 2.

 

 

 

No 24VAC supply to power board.

Check wiring from - T2 to powerboard and fuse.

 

 

No +12V output from powerboard.

Replace powerboard or isolate excessive load on

 

 

the board.

 

 

 

 

 

 

NO RUN PERM displayed

 

No liquid flow through the evaporator.

Ensure that liquid pumps are running. Valves are

(No run permissive)

 

correctly set and flow is established.

 

 

 

 

 

 

 

 

 

Check that the flow switch is functional and is

 

 

Flow switch or cycling contacts are

 

 

 

 

installed according to the manufacturer’s instructions.

 

 

Flow switch contacts are not made.

 

 

 

not made.

 

Check cycling contacts.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SYS # HIGH OIL TEMP

 

Poor airflow through the condenser

Check for airflow restrictions caused by blockages on

 

 

coils.

intake faces of air coils.

 

 

 

Measured temperature incorrect.

Check oil temp sensor and wiring.

 

Chiller FAULT: LOW

 

Ambient air temperature is lower

Use the ‘ambient temp.’ key to display the

AMBIENT TEMP displayed

 

than the programmed operating

temperature and confirm that the displayed value is

 

 

limit.

approximately correct. The warning message should

 

 

 

 

clear when the ambient air temperature rises above

 

 

 

 

the programmed operating limit.

 

 

 

 

 

Check the programmed settings are correct for the

 

 

 

 

options fitted to the unit.

 

 

 

Measured temperature is incorrect.

Check ambient sensor and wiring.

 

Chiller FAULT: HIGH

 

Ambient air temperature is higher

Use the ‘ambient temp.’ key to display the

AMBIENT TEMP displayed

 

than the programmed operating limit.

temperature and confirm that the displayed value is

 

 

 

 

approximately correct. The warning message should

 

 

 

 

clear when the ambient air temperature falls below

 

 

 

 

the programmed operating limit.

 

 

 

 

 

Check that the programmed settings are correct for

 

 

 

 

the options fitted to the unit.

 

 

 

RecirculatedResid. heat airis notis affectingbeing dissipatedthe sensor. .

Check fans are operating correctly and the rotation is

 

 

correct. Check for airflow recirculation.

 

 

 

 

 

 

 

 

Measured temperature is incorrect.

Check ambient sensor and wiring.

 

Chiller FAULT: LOW

 

Leaving liquid drops below the

Check for restrictions in the liquid flow line.

WATER TEMP displayed

 

programmed low limit faster than the

Check that the liquid flow is stable.

 

 

 

unit can unload.

 

 

 

 

Unit is not unloading.

Check the voltage to the unloader valve solenoid.

 

 

Check that the compressor unloads correctly.

 

 

 

 

 

 

Measured temperature is incorrect.

Check water temp sensor and wiring.

 

Chiller FAULT: VAC

 

 

 

Check main supply is stable and within allowable

UNDERVOLTAGE

 

Poor main supply voltage.

limits.

 

displayed.

 

 

 

Check for voltage dip on compressor start.

200

YORK INTERNATIONAL

Page 200
Image 200
York YCAS0130 manual Troubleshooting Guide