Micro Panel Contents

The Pilot Solenoid is also used as a low superheat safety device when EEV is selected as the expansion valve type, for YCAL units only. While the system is running and not in a pumpdown mode the Pilot Solenoid will close if the suction superheat falls below 4.0º F. The Pilot Solenoid will open again when the superheat rises above 7.0º F. This safety device is ignored for the first 30 seconds of system run time. If the Pilot Solenoid is closed 10 times in 2 minutes on the safety device, the low superheat safety will be triggered.

LOW SUPERHEAT CUTOUT SAFETY

The Low Superheat Cutout is to protect the compressors from liquid floodback due to low suction superheat. This safety is only active when EEV is selected as the expan- sion valve type. This safety is ignored for the first 30 seconds of system run time.

This safety can be triggered by two events. The first is when the suction superheat is less than 0.5º F (1.1ºC) for 3 seconds. The second, only applies to YCAL units, is when the Pilot Solenoid is closed 10 times in 2 min- utes due to low superheat. Following are the safety fault messages for all systems:

S Y S

1

L O W

S U P E R H E A T

S Y S

2

L O W

S U P E R H E A T

 

 

 

 

SENSOR FAILURE CUTOUT SAFETY

The Sensor Failure Cutout is to prevent the EEV from running when the sensors measuring superheat are not functioning properly. This safety is only active when EEV is selected as the expansion valve type. This safety is ignored for the first 15 seconds of system run time.

This safety will shutdown a system if either suction tem- perature or suction pressure sensors read out of range high or low. This condition must be present for 3 seconds to cause a system shutdown. This safety will lock out a system the first time and will not allow automatic restart- ing. Following are the messages for all systems:

S Y S

1

S E N S O R

F A I L U R E

S Y S

2

S E N S O R

F A I L U R E

 

 

 

 

FORM 201.19-NM1 (204)

OPERATING DATA DISPLAYS

The following display relating to EEV operation is avail- able under each systems Data Key: EEV Output% and Suction Superheat.

S Y S X E E V = X X X . X %

S U C T S H E A T = X X X . X º F

HISTORY DATA DISPLAYS

The following display relating to EEV operation is avail- able under each systems Data Key: EEV Output% and Suction Superheat.

S Y S X E E V = X X X . X %

S U C T S H E A T = X X X . X º F

OPERATING DATA PRINTOUT

Pressing the PRINT key and then the OPER DATA key allows the operator to obtain a printout of current system operating parameters. When the OPER DATA key is pressed, a snapshot will be taken of system operating conditions and panel programming selections. This data will be temporarily stored in memory and transmission of this data will begin to the printer. The following items are added to the standard operational data printout when EEV is selected:

SYSTEM 1 DATA

 

 

 

COMPRESSORS STATUS

 

 

OFF

RUN TIME

0- 0- 0- 0 D-H-M-S

MOTOR CURRENT

 

0 AMPS 0

%FLA

SUCTION PRESSURE

 

125

PSIG

DISCHARGE PRESSURE

 

131

PSIG

OIL PRESSURE

 

130

PSIG

FAN DISCHARGE PRESS

 

254

PSIG(B HR)

SUCTION TEMPERATURE

 

68.4

DEGF

DISCHARGE TEMPERATURE

68.8

DEGF

OIL TEMPERATURE

 

68.8

DEGF

SAT SUCTION TEMP

 

71.8

DEGF

SUCTION SUPERHEAT

 

3.4

DEGF

SAT DISCHARGE TEMP

 

74.5

DEGF

DISCHARGE SUPERHEAT

 

6.3

DEGF

SLIDE VALVE STEP

 

 

0

EEV OUTPUT

 

0.0 %(EEV)

COOLER INLET REFRIG

 

44.6

DEGF

LIQUID LINE SOLENOID

 

 

OFF

ECONOMIZER TXV SOLENOID

 

OFF(YCAS)

OIL COOLING SOLENOID

 

 

OFF(YCWS)

HEAT RECOVERY SOLENOID

 

OFF(B HR)

DISCHARGE COOLING SOLENOID

OFF(EC,LT)

CONDENSER FAN STAGE

 

 

OFF

COMPRESSOR HEATER

 

 

ON

WYE-DELTA RELAY

 

 

OFF