York YCAS0130 manual Micro Panel Contents

Models: YCAS0130

1 204
Download 204 pages 14.22 Kb
Page 178
Image 178

Micro Panel Contents

FORM 201.19-NM1 (204)

TABLE 3 – CONDENSER FAN CONTROL AND FAN CONTACTOR DATA FOR DXST UNITS WITH 4 FANS/SYSTEM

 

Fan

Fans

ON * **

OFF *

Fan

Wire

Relay

 

Conditions

Conditions

Board

 

Stage

 

DP

DP & OAT

Contactor

Number

Output*

S

1

1

>230 PSIG

<160 PSIG & <60°F

9M

130

15

 

Y

2

5 & 7

>250 PSIG

<180 PSIG & <65°F

11M & 12M

132

10

 

S

3

1, 5, & 7

>265 PSIG

<195 PSIG & <70°F

9M, 11M, & 12M

130 & 132

10 & 15

 

1

4

1, 3, 5, & 7

>275 PSIG

<205 PSIG & <75°F

9M, 10M, 11M, & 12M

130, 131, & 132

10, 14, & 15

 

S

1

2

>230 PSIG

<160 PSIG & <60°F

15M

230

15

 

Y

2

6 & 8

>250 PSIG

<180 PSIG & <65°F

17M & 18M

232

10

 

S

3

2, 6, & 8

>265 PSIG

<195 PSIG & <70°F

15M, 17M, & 18M

230 & 232

10 & 15

 

2

4

2, 4, 6, & 8

>275 PSIG

<205 PSIG & <75°F

15M, 16M, 17M, & 18M

230, 231, & 232

10, 14, & 15

 

* Sys 1 Outputs are on Relay Output Board #1

** At ambients above 85ºF, Stages 3 and 4 will both turn on at 240 PSIG.

Sys 2 Outputs are on Relay Output Board #2

 

 

 

 

 

TABLE 4 – CONDENSER FAN CONTROL AND FAN CONTACTOR DATA FOR DXST UNITS WITH 5 FANS/SYSTEM

 

 

Fan

Fans

ON * **

OFF *

Fan

Wire

Relay

 

 

Conditions

Conditions

Board

 

 

Stage

 

DP

DP & OAT

Contactor

Number

Output*

 

S

1

1

>230 PSIG

<160 PSIG & <60°F

9M

130

15

 

 

Y

2

7 & 9

>250 PSIG

<180 PSIG & <65°F

12M & 13M

132

10

 

 

S

3

1, 7, & 9

>265 PSIG

<195 PSIG & <70°F

9M, 12M, & 13M

130 & 132

10 & 15

 

1

4

3, 5, 7, & 9

>275 PSIG

<205 PSIG & <75°F

10M, 11M, 12M, & 13M

131 & 132

14 & 15

 

5

1, 3, 5, 7, & 9

>285 PSIG

<210 PSIG & <80°F

9M, 10M, 11M, 12M, &13M

130, 131, & 132

10, 14, & 15

 

 

S

1

2

>230 PSIG

<160 PSIG & <60°F

15M

230

15

 

 

Y

2

8, & 10

>250 PSIG

<180 PSIG & <65°F

18M & 19M

232

10

 

 

S

3

2, 8, &10

>265 PSIG

<195 PSIG & <70°F

15M, 18M, & 19M

230 & 232

10 & 15

 

 

2

4

4, 6, 8, & 10

>275 PSIG

<205 PSIG & <75°F

16M, 17M, 18M, 19M

231 & 232

14 & 15

 

5

2, 4, 6, 8, & 10

>285 PSIG

<210 PSIG & <80°F

15M, 16M, 17M, 18M, & 19M

230, 231, & 232

10, 14, & 15

 

* Sys 1 Outputs are on Relay Board #1

** At ambients above 85ºF, Stages 3, 4 and 5 will both turn on at 240 PSIG.

 

Sys 2 Outputs are on Relay Output Board #2

 

 

 

 

 

178

YORK INTERNATIONAL

Page 178
Image 178
York YCAS0130 manual Micro Panel Contents, CONDENSER FAN CONTROL AND FAN CONTACTOR DATA FOR DXST UNITS WITH 4 FANS/SYSTEM