![](/images/new-backgrounds/1044861/44861395x1.webp)
Maintenance
FORM
GENERAL PERIODIC MAINTENANCE CHECKS
STANDARD UNITS
SERVICE SCHEDULE | MINOR SERVICE | MAJOR SERVICE | |
All items under Minor Service plus: | |||
|
| ||
Unit general: | Check thermal insulation. | Check main structure. | |
| Check vibration isolators. | Check | |
Refrigerant systems general: | Check relief valves. | Check solenoid valves. | |
| Check fusible plugs. |
| |
| Check for pipework damage. |
| |
| Check for leaks. |
| |
| Check moisture indicator. |
| |
| Check suction superheat. |
| |
| Check economizer superheat. |
| |
| Check liquid subcooling. |
| |
Compressors / Oil separator: | Check oil level. |
| |
| Check oil pressure. |
| |
| Check slide valve operation. |
| |
| Check compressor heater. |
| |
| Check condition of oil. |
| |
| Check discharge superheat. |
| |
Evaporator | Check water flow. | Check water pH / glycol strength. | |
| Check water pressure drop. |
| |
| Check heater. |
| |
Air cooled condensers: | Check for airflow obstructions. | Brush fins. Clean with mild, low | |
|
| pH cleaner. | |
| Check fins. | Check fan motor bearings. | |
| Check fans and fan guards. |
| |
Power & Control system general: | Check panel condition. | Check all connections. | |
| Check mains and control wiring. | Check compressor contactors. | |
| Check sensor location. | Check fan contactors / overloads. | |
| Check mechanical HP cutouts. | Check sensor / transducer calibration. | |
| Check emergency stop. | Check motor protectors. | |
| Check overload devices. |
| |
Microprocessor controls: | Check fault history. | Check fan control function. | |
| Check program settings. | Check ambient | |
| Check HP / LP cutout functions |
| |
| Check |
| |
| Check load / unload function. |
|
198 | YORK INTERNATIONAL |