Technical Data

ELECTRICAL DATA

FORM 201.19-NM1 (204)

LD05549

OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION AND INDIVIDUAL SYSTEM CIRCUIT BREAKERS

Suitable for:

Y - Start and

Across-The-Line-Start

One field provided power supply circuit to the unit. Field connections to factory provided Non-Fused Disconnect Switch (Opt), or Terminal Block (Opt). Factory connections to Circuit Breakers on Terminal Blocks in each of the two Power Panels.

See page 62 for notes.

OPTIONAL SINGLE-POINT POWER SUPPLY WITH INDIVIDUAL SYSTEM CIRCUIT BREAKERS –

2 COMPRESSOR UNITS

(One Field Provided Power Supply Circuit to the chiller. Field connections to Factory Provided Terminal Block (standard) or Non-Fused Disconnect (option).

Individual System Circuit Breakers in each Motor Control Center10)

CHILLER

 

 

 

 

 

 

FIELD-SUPPLIED WIRING

 

 

 

FIELD PROVIDED POWER SUPPLY

 

 

FACTORY PROVIDED (LUGS) WIRE RANGE 7

MODEL

VOLTS

 

 

 

YCAS

 

MCA1

MIN NF

OVER-CURRENT

PROTECTION13

 

STANDARD

OPTIONAL NF

 

 

 

DISC SW2, 9

MIN.3, 5

 

MAX.4, 6

 

TERMINAL BLOCK

DISC. SWITCH

 

200

619.3

800

700

 

700

 

(3) 2/0 - 500

(3) 2/0-400

0130EC

230

543.9

600

600

 

700

 

(2) 2/0 - 500

(2) 250-500

380

329.8

400

400

 

450

 

(2) 1/0 - 300

(2) 3/0-250

 

460

272.8

400

300

 

350

 

2/0 - 500

(2) 3/0-250

 

575

217.4

250

250

 

300

 

2/0 - 500

# 6 - 350

 

200

665.9

800

800

 

800

 

(3) 2/0 - 500

(3) 2/0-400

0140EC

230

584.4

800

700

 

800

 

(3) 2/0 - 500

(2) 250-500

380

354.3

400

400

 

450

 

(2) 1/0 - 300

(2) 3/0-250

 

460

293.0

400

350

 

400

 

(2) 1/0 - 300

(2) 3/0-250

 

575

233.6

250

300

 

300

 

2/0 - 500

# 6 - 350

 

200

698.9

800

800

 

800

 

(3) 2/0 - 500

(3) 2/0-400

0150EC

230

612.4

800

700

 

800

 

(3) 2/0 - 500

(3) 2/0-400

380

371.4

400

450

 

500

 

(2) 2/0 - 500

(2) 3/0-250

 

460

307.0

400

350

 

400

 

(2) 1/0 - 300

(2) 3/0-250

 

575

245.6

400

300

 

300

 

2/0 - 500

(2) 3/0-250

 

200

729.4

800

1000

 

800

 

(3) 2/0 - 500

(3) 2/0-400

0160EC

230

638.4

800

800

 

800

 

(3) 2/0 - 500

(3) 2/0-400

380

387.2

600

450

 

500

 

(2) 2/0 - 500

(2) 250-500

 

460

320.0

400

400

 

400

 

(2) 1/0 - 300

(2) 3/0-250

 

575

256.6

400

300

 

300

 

2/0 - 500

(2) 3/0-250

 

200

761.9

800

1000

 

1000

 

(3) 2/0 - 500

(3) 2/0-400

0170EC

230

667.2

800

800

 

800

 

(3) 2/0 - 500

(3) 2/0-400

380

404.7

600

450

 

500

 

(2) 2/0 - 500

(2) 250-500

 

460

335.0

400

400

 

400

 

(2) 1/0 - 300

(2) 3/0-250

 

575

267.8

400

300

 

350

 

2/0 - 500

(2) 3/0-250

 

200

787.9

1000

1000

 

1000

 

N/A

N/A

0180EC

230

690.2

800

800

 

800

 

N/A

N/A

380

418.7

600

500

 

500

 

(2) 2/0 - 500

(2) 250-500

 

460

347.0

400

400

 

450

 

(2) 1/0 - 300

(2) 3/0-250

 

575

276.8

400

350

 

350

 

(2) 1/0 - 300

(2) 3/0-250

 

200

851.5

1000

1000

 

1000

 

N/A

N/A

0200EC

230

748.5

800

1000

 

800

 

N/A

N/A

380

455.3

600

600

 

500

 

(2) 2/0 - 500

(2) 250-500

 

460

375.3

400

450

 

450

 

(2) 2/0 - 500

(2) 3/0-250

 

575

298.8

400

350

 

350

 

(2) 1/0 - 300

(2) 3/0-250

 

200

891.5

1000

1000

 

1000

 

N/A

N/A

0210EC

230

782.3

1000

1000

 

1000

 

N/A

N/A

380

475.3

600

600

 

600

 

(2) 2/0 - 500

(2) 250-500

 

460

392.8

600

450

 

500

 

(2) 2/0 - 500

(2) 250-500

 

575

312.5

400

350

 

400

 

(2) 1/0 - 300

(2) 3/0-250

 

200

923.5

1000

1200

 

1200

 

N/A

N/A

0230EC

230

809.3

1000

1000

 

1000

 

N/A

N/A

380

491.3

600

600

 

600

 

(2) 2/0 - 500

(2) 250-500

 

460

406.8

600

450

 

500

 

(2) 2/0 - 500

(2) 250-500

 

575

323.5

400

400

 

450

 

(2) 1/0 - 300

(2) 3/0-250

See page 62 for Electrical Data footnotes.

56

YORK INTERNATIONAL

Page 56
Image 56
York YCAS0130 manual PROTECTION13 Standard Optional NF Disc SW2