York DIMENSIONS - YCAS0130 - YCAS0180 SI, Technical Data, Edge Of Unit To Cooler Connection

Models: YCAS0130

1 204
Download 204 pages 14.22 Kb
Page 84
Image 84

Technical Data

FORM 201.19-NM1 (204)

All dimensions are in mm unless otherwise noted.

DIMENSIONS – YCAS0130 - YCAS0180 (SI)

LD03745a

46 (EDGE OF UNIT TO COOLER CONNECTION

 

MODELS

MODELS

 

DIMENSION

130 - 140

150 - 180

 

P

438

457

 

NOTES:

1.Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reli- able operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable air flow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high pressure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; control panel end to wall - 1.2m; top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be higher than the unit.

FIG. 24 – MODEL YCAS0130 - 0180 DIMENSIONS (SI)

84

YORK INTERNATIONAL

Page 84
Image 84
York manual DIMENSIONS - YCAS0130 - YCAS0180 SI, Technical Data, All dimensions are in mm unless otherwise noted