York YCAS0130 manual This message indicates the EEV preheat % and the suc- tion superheat

Models: YCAS0130

1 204
Download 204 pages 14.22 Kb
Page 155
Image 155

S Y S

#

O I L =

1 7 5

P S

I

G

S P =

6 2 D P =

2 7 1

P S

I

G

 

 

 

 

 

 

 

This message indicates the system oil pressure, suc- tion pressure, and discharge pressure at the time of the fault.

S Y S

#

O I L =

1

5

4 .

8

°

F

S T =

3

9 . 0 D T = 1

2

3 .

7

°

F

 

 

 

 

 

 

 

 

 

This message shows the system oil temperature, suction temperature, and discharge temperature at the time of the fault.

S # S A T S U C T

= 3 4

.

7

°

F

S U C T S H E A T

= 1 0

.

5

°

F

 

 

 

 

 

 

These messages indicate compressor suction gas sat- uration temperature and superheat at the time of the fault.

S # S A T D S C H =

1 2 9 °

F

D S C H S H E A T

= 6 2 . 8 °

F

 

 

 

This message indicates compressor discharge gas sat- uration temperature and superheat at the time of the fault.

S Y S # S V S T E P =

4 0

 

 

This message indicates the compressor slide valve po- sition at the time of the fault. 0 steps equals minimum capacity and 75 steps equals fully loaded.

S Y S X E E V

= 3 7 . 4 %

S U C T S H E A T

= 1 0 . 2 º F

 

 

This message indicates the EEV preheat % and the suc- tion superheat.

S Y S

# C O O L E R I N L E T

 

R E F R I G T E M P = 2 8 . 2

° F

 

 

 

This message, which is only displayed if the unit is in R-407C mode, indicates the refrigerant temperature at the inlet of the evaporator.

FORM 201.19-NM1 (204)

S Y S # L L S V I S

O N

E C O N T X V S O L I S

O F F

 

 

This message indicates the EEV PILOT Solenoid Valve and the economizer Thermal Expansion Valve Solenoid Valve position: ON = Energized / OFF = De-Energized (OFF) at the time of the fault.

S Y S # F A N S T A G E

3

C O M P H E A T E R I S

O F F

 

 

This message indicates the stage of condenser fan op- eration on the system and the status of the compressor heater at the time of the fault. See Section 8.4 for details of fan staging.

S Y S # W Y E - D E L T A

O N

 

 

This message indicate whether the WYE-DELTA out- put to the compressor was energized at the time of the fault

S Y S

X

D S C H C L S V

OFF

S Y S

X

W Y E - D E L T A

OFF

 

 

 

 

This message indicates whether the discharge cooling solenoid was energized at the time of the fault and if the WYE-DELTA output to the compressor was energized. (Low Temperature Glycol Chillers Only)

8

YORK INTERNATIONAL

155

Page 155
Image 155