FORM
OPERATING LIMITATIONS AND SOUND POWER DATA
OPERATING LIMITATIONS – ENGLISH UNITS
|
|
|
| MIN | MAX |
| LEAVING CHILLED LIQUID TEMP ( °F) | 40.1 | 59 | ||
|
|
|
|
| |
| CHILLED WATER TEMP DIFFERENCE ( °F) | 5.5 | 18 | ||
| WATER SIDE PRESSURE (PSIG) |
|
| 150 | |
| REFRIGERANT SIDE PRESSURE (PSIG) |
| 300 | ||
|
|
|
|
|
|
|
|
|
| EVAPORATOR FLOW | |
| MODEL |
| GALLONS/MINUTE | ||
| YCAS |
| MIN. | MAX. | |
|
|
|
|
|
|
| 0130EC |
| 141 | 403 | |
|
|
|
|
| |
| 0140EC |
| 141 | 403 | |
| 0150EC |
| 180 | 769 | |
| 0160EC |
| 141 | 403 | |
| 0170EC |
| 180 | 768 | |
| 0180EC |
| 180 | 768 | |
|
|
|
|
| |
| 0200EC |
| 180 | 768 | |
| 0210EC |
| 180 | 768 | |
|
|
|
|
| |
| 0230EC |
| 180 | 768 | |
| AIR |
| STANDARD FANS | 0 | 115* |
| ENTERING |
| HIGH PRESS. FANS | 0 | 115* |
| CONDENSER (°F) |
| STANDARD FANS |
| 20 |
| FAN |
|
| ||
|
|
|
|
| |
|
|
|
|
|
|
| AVAILABLE STATIC |
| HIGH PRESS. FANS | OPTION 1 | 85 |
| PRESSURE (Pa) |
| HIGH PRESS. FANS | OPTION 2 | 150 |
|
|
| LOW NOISE (4 PL) |
| 10 |
|
|
|
|
| |
| ELECTRICAL THREE PHASE 60 Hz (V) | 200 |
| ||
|
|
|
| 230 |
|
|
|
|
|
|
|
|
|
|
| 380 |
|
|
|
|
|
|
|
|
|
|
| 460 |
|
|
|
|
| 575 | 440 |
|
|
|
|
|
|
* Maximum Ambient w/ High Ambient Kit is 130°F.
OPERATING LIMITATIONS – SI UNITS
|
|
|
| MIN | MAX |
| LEAVING CHILLED LIQUID TEMP ( °C) | 4.5 | 15 | ||
|
|
|
|
| |
| CHILLED WATER TEMP DIFFERENCE ( °C) | 3 | 10 | ||
| WATER SIDE PRESSURE (BAR) |
| – | 10 | |
|
|
|
|
| |
| REFRIGERANT SIDE PRESSURE (BAR) | – | 20 | ||
|
|
|
|
|
|
| MODEL |
| EVAPORATOR FLOW | ||
|
| LITERS/SECOND | |||
| YCAS |
| |||
|
|
|
| ||
|
| MIN. | MAX. | ||
|
|
|
| ||
|
|
|
|
|
|
| 0130EC |
| 8.9 | 25.43 | |
|
|
|
|
|
|
| 0140EC |
| 8.9 | 25.43 | |
| 0150EC |
| 11.3 | 48.45 | |
| 0160EC |
| 8.9 | 25.43 | |
| 0170EC |
| 11.3 | 48.45 | |
| 0180EC |
| 11.3 | 48.45 | |
|
|
|
|
| |
| 0200EC |
| 11.3 | 48.45 | |
| 0210EC |
| 11.3 | 48.45 | |
|
|
|
|
| |
| 0230EC |
| 11.3 | 48.45 | |
| AIR |
|
|
| |
| ENTERING | STANDARD FANS | 46 | ||
| CONDENSER (°C) |
|
|
| |
|
|
|
|
|
|
| FAN | STANDARD FANS |
| 20 | |
| AVAILABLE STATIC |
| HIGH PRESS. FANS | OPTION 1 | 85 |
| PRESSURE (Pa) | HIGH PRESS. FANS | OPTION 2 | 150 | |
|
|
| SLOW SPEED FANS |
| 10 |
|
|
|
| ||
| ELECTRICAL THREE PHASE 60 Hz (V) | 200 |
| ||
|
|
|
|
|
|
|
|
|
| 230 |
|
|
|
|
|
|
|
|
|
|
| 380 |
|
|
|
|
| 460 |
|
|
|
|
|
|
|
|
|
|
| 575 |
|
|
|
|
|
|
|
* Maximum Ambient w/ High Ambient Kit is 54°C.
7
YORK INTERNATIONAL | 53 |