
Operation
FORM
OPERATION
GENERAL DESCRIPTION
The units are designed to work independently, or in conjunction with other equipment via a YORK ISN building management system or other automated con- trol system. When operating, the unit controls monitor the chilled liquid system temperature at the unit and take the appropriate action to maintain this temperature within desired limits. This action will involve running one or more compressors at a suitable load step to match the cooling effect of the refrigerating systems to the heat load on the liquid system. The heat removed from the chilled liquid is then rejected from the air cooled condenser coils.
The following sections give an overview of the operation of the unit. For detailed information, reference should be made to the Chiller Control Panel Programming and Data Access Operating Instructions for the unit (pages 122 - 192).
Check the main power supplies to the unit are ‘ON’, all refrigerant service valves are open
Press the ‘STATUS’ key on the keypad and then switch the unit ON/OFF switch below the keypad to the ON position.
The controller will perform a
The display will show the
NORMAL RUNNING AND CYCLING
Once the unit has been started, all operations are fully automatic. After an initial period at minimum capacity on the lead compressor, the control system will adjust the unit load depending on the chilled liquid temperature and rate of temperature change. If high heat load is pres- ent, the controller will increase the capacity of the lead compressor and/or
If very little heat load is present, the lead compressor will continue at minimum capacity or may simply stop again to avoid overcooling the liquid. If the latter is the case, one compressor will restart automatically should the liquid temperature rise again.
Once a compressor is running, discharge pressure rises as refrigerant is pumped into the air cooled condenser coils. This pressure is controlled by stages of fans to ensure maximum unit efficiency while maintaining suf- ficient pressure for correct operation of the condensers and expansion valves.
When a compressor is running, the controller monitors oil pressure, motor current, and various other system parameters such as discharge pressure, chilled liquid temperature, etc. Should any problems occur, the control system will immediately take appropriate action and display the nature of the fault (Section 8).
SHUTDOWN
The unit can be stopped at any time by switching the UNIT ON/OFF switch just below the keypad to the OFF position. The compressor heater will energize to prevent refrigerant condensing in the compressor rotors. If ambient temperatures are low, the evaporator heater mats will also energize to prevent the possibility of liq- uid freezing in the vessels. The mains power to the unit should not normally be switched OFF, even when the unit is not required to run.
The system switches
If mains power must be switched OFF, (for extended maintenance or a shutdown period), the compressor suc- tion, discharge and motor cooling service stop valves should be closed (clockwise) and if there is a possibility of liquid freezing due to low ambient temperatures, the evaporators should be drained. Valves should be opened and power must be switched on for at least 8 Hours (36 Hours if ambient temperature is over 86°F [30°C]) before the unit is restarted.
46 | YORK INTERNATIONAL |