York YCAS0130 manual This message indicates the EEV preheat % and the suc- tion superheat

Models: YCAS0130

1 204
Download 204 pages 14.22 Kb
Page 151
Image 151

S Y S X E E V

= 3 7

.

4

%

S U C T S H E A T

= 1 0

.

2

° F

 

 

 

 

 

This message indicates the EEV preheat % and the suc- tion superheat.

S Y S # R U N T

I M E

 

1 - 3 - 4 8 - 1

7 D

- H - M - S

 

 

 

This message displays the accumulated Run Time since the last start in Days (D), Hours (H), Minutes (M), and Seconds (S).

S Y S # L L S V I S

O N

E C O N T X V S O L I S

O N

 

 

This message indicates the Liquid Line Solenoid Valve and the economizer TXV solenoid valve position: ON = Energized/Open, OFF = De-energized/Closed.

S Y S # F A N S T A G E

3

C O M P H E A T E R I S

O N

 

 

This message advises the stage of condenser fan op- eration on this system and the status of the compressor heater. See Section 8.4 for details of fan staging.

Once the System Data sequence has been repeated for the second system, pressing the or key again will loop back to the beginning to the Load/Unload Timer display. To leave the sequence at any point, press a key from another section of the keypad.

SOFTWARE VERSION

The software version may be viewed by pressing the * key.

The software version will be displayed similar to the sample below:

S O F T W A R E V E R S I O N

C . A C S . 0 9 . 0 8

FORM 201.19-NM1 (204)

4.4OPERATING DATA – REMOTE PRINTOUT

The follow text shows a typical example printout obtained by pressing the Operating Data key with an optional printer attached. In this case, an example is shown for a YCAS 2 System Chiller.

YORK INTERNATIONAL CORPORATION

MILLENNIUM SCREW CHILLER

 

UNIT STATUS

 

 

2:04PM 01 JUN 02

 

SYS 1

NO COOLING LOAD

SYS 2

COMPRESSOR RUNNING

OPTIONS

 

 

 

 

CHILLED LIQUID

 

 

 

WATER

AMBIENT CONTROL

 

STANDARD

REFRIGERANT TYPE

 

 

R-22

UNIT TYPE

 

 

 

YCAS

MOTOR CURRENT AVERAGING

ENABLED

HEAT RECOVERY

 

 

DISABLED

PROGRAM VALUES

 

 

 

DSCH PRESS CUTOUT

 

399

PSIG

DSCH PRESS UNLOAD

 

375

PSIG

SUCT PRESS CUTOUT

 

44

PSIG

HIGH AMBIENT CUTOUT

130.0

DEGF

LOW AMBIENT CUTOUT

25.0

DEGF

LEAVING LIQUID CUTOUT

36.0

DEGF

MOTOR CURRENT UNLOAD

 

100

%FLA

ANTI RECYCLE TIME

 

600

SECS

LOCAL/REMOTE MODE

 

REMOTE

LEAD/LAG CONTROL

AUTOMATIC

UNIT DATA

 

 

 

LEAVING LIQUID TEMP

49.0

DEGF

RETURN LIQUID TEMP

58.2

DEGF

SETPOINT

42.0 +/-

2.0 DEGF

REMOTE SETP

42.0 +/-

2.0 DEGF

AMBIENT AIR TEMP

74.8

DEGF

LEAD SYSTEM

 

 

 

SYS 2

EVAPORATOR PUMP

 

 

ON

EVAPORATOR HEATER

 

 

OFF

ACTIVE REMOTE CONTROL

 

 

NONE

SOFTWARE VERSION

C.ACS.09.00

SYSTEM 1 DATA

 

 

 

COMPRESSORS STATUS

 

 

OFF

RUN TIME

0- 0- 0- 0 D-H-M-S

MOTOR CURRENT

0 AMPS

0 %FLA

SUCTION PRESSURE

 

125

PSIG

DISCHARGE PRESSURE

 

131

PSIG

OIL PRESSURE

 

 

130

PSIG

SUCTION TEMPERATURE

68.4

DEGF

DISCHARGE TEMPERATURE

68.8

DEGF

OIL TEMPERATURE

68.8

DEGF

SAT SUCTION TEMP

71.8

DEGF

8

YORK INTERNATIONAL

151