Instructions to installation
Piping Connection
AD092XLERA
AD122XLERA
AD142XLERA
AD182XLERA
Flare connection | Gas pipe | |
|
| |
Indoor |
| Outdoor |
Unit |
| unit |
| Liquid | |
| pipe | |
| Flare connection | |
Flare connection | Gas pipe | |
| A | |
|
| |
Indoor |
| Outdoor |
Unit |
| unit |
| Liquid | |
| pipe | |
| Flare connection |
To gas pipe
A(adaptor, from 9.52 to 12.7)
To outdoor unit
Pipe expansion dimensions as follows:
Pipe diameter ÿ | Size A (mm) |
6.35 mm (1/4") | 0.8 ~ 1.5 |
9.52 mm (3/8") | 1.0 ~ 1.8 |
12.7 mm (1/2") | 1.2 ~ 2.0 |
|
|
Correct |
|
| Incorrect | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Slope Damage Bur Partial Overlong
A
Pipe expander
The connection of indoor unit pipes must use double spanners.
The installing torque shall be as given in the following table.
Connecting pipe | Installing torque | Increased installing |
O.D.(mm) | torque | |
ÿ6.35 | 11.8 | 13.7 (1.4 |
ÿ9.52 | 24.5 | 29.4 (3.0 |
ÿ12.70 | 49.0 (5.0 | 53.9 (5.5 |
20