Haier AD122XLERA Instructions to installation, Piping Connection, Connecting pipe, O.D.mm, ΓΏ6.35

Models: AD092XLERA AD122XLERA AD142XLERA AD182XLERA

1 28
Download 28 pages 33.88 Kb
Page 22
Image 22
Piping Connection

Pipe expansion dimensions as follows: Instructions to installation

Piping Connection

AD092XLERA

AD122XLERA

AD142XLERA

AD182XLERA

Flare connection

Gas pipe

3-way valve

 

 

Indoor

 

Outdoor

Unit

 

unit

 

Liquid

2-way valve

 

pipe

 

Flare connection

Flare connection

Gas pipe

3-way valve

 

A

 

 

Indoor

 

Outdoor

Unit

 

unit

 

Liquid

2-way valve

 

pipe

 

Flare connection

To gas pipe Connecting pipeInstalling torqueIncreased installingO.D.(mm)torque (N-m)ÿ6.35

A(adaptor, from ÿ9.52 9.52 to ÿ12.70 12.7)

To outdoor unit

Pipe expansion dimensions as follows:

Pipe diameter ÿ

Size A (mm)

6.35 mm (1/4")

0.8 ~ 1.5

9.52 mm (3/8")

1.0 ~ 1.8

12.7 mm (1/2")

1.2 ~ 2.0

 

 

Correct

 

 

Incorrect

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slope Damage Bur Partial Overlong

A Manual background

Pipe expander

Manual background The connection of indoor unit pipes must use double spanners.

Manual background The installing torque shall be as given in the following table.

Connecting pipe

Installing torque

Increased installing

O.D.(mm)

(N-m)

torque (N-m)

ÿ6.35

11.8 (1.2kgf-m)

13.7 (1.4 kgf-m)

ÿ9.52

24.5 (2.5kgf-m)

29.4 (3.0 kgf-m)

ÿ12.70

49.0 (5.0 kgf-m)

53.9 (5.5 kgf-m)

Double-spanner operation

20

Page 22
Image 22
Haier AD122XLERA Instructions to installation, Piping Connection, Pipe expansion dimensions as follows, Connecting pipe