4 Wiring of indoor unit

 Communication cable (Shield wire): Instructions to installation

4 Wiring of indoor unit

The distance between the signal wires and the power cabes should be at least 50mm.

1(L)

2(N)

P

Q

A

B

C

1(L)

2(N)

P

Q

A

B

C

To wired controller(A,B,C)

To other indoor unit

Power cable : H05RN-F 3G 2.5 mm2Waring: Communication cable (Shield wire):

H05RN-F 2X1.5 mm2

 

L N

 

 

 

C1 C2

 

 

 

 

Power cable : H05RN-F 3G 2.5 mm2

 

 

 

 

(P Q)

To outdoor unit

Waring:

1.Incorrect address setting will cause abnormal to the system. 2.Communication cable must be use sheilded type.

Failure code

TROUBLE SHOOTING

FAILURE CODE

POSSIBLE REASONS

(indoor unit)

(CHECK THE WIRED

REMOTE CONTROLLER)

 

 

 

Faulty temperature sensor Tai

01

*

Sensor disconnected, or broken, or at wrong

position, or short circuit

 

 

 

 

 

 

 

Faulty temperature sensor Tc1

02

*

Sensor disconnected, or broken, or at wrong

position, or short circuit

 

 

 

 

 

 

 

Faulty temperature sensor Tc2

03

*

Sensor disconnected, or broken, or at wrong

position, or short circuit

 

 

 

 

 

 

Faulty temperature sensor Tm

04

*

Sensor disconnected, or broken, or at wrong

position, or short circuit

 

 

 

 

 

 

 

Faulty EEPROM on indoor

05

 

Faulty indoor unit PCB

unit PCB

 

 

 

 

Abnormal communication

 

*

Wrong connection, or the wires be

06

disconnected, or wrong address setting of

between indoor and outdoor unit

indoor units, or faulty power supply or faulty

 

 

 

PCB

 

 

 

 

23

Page 25
Image 25