Instructions to installation
| Pipe and insulation material |
|
|
Pipe | Rigid PVC pipe VP31.5mm (internal diameter) |
|
|
Insulation | Foamed PE with thickness above 7mm |
|
|
|
|
| Hose |
Drain pipe size: ÿ19.05mm2 (3/4") PVC pipe.
The hose is used for adjusting the
Directly stretch the hose to install without making any deformation. | |
The soft end of the hose must be fastened with a hose clamp. |
|
Please apply the hose on horizontal part | Hose |
|
Insulation treatment:
Wrap the hose and its clamp until to the indoor unit without any clearance with insulating material, as shown in the figure.
Subsidiary insulation
Hose clamp
Insulation
Rigid PVC pipe
Drain confirmation
During trial run, check that there is no leakage at the pipe connection part during water draining even in winter.
Allowable pipe length and drop
These parameters differ according to the outdoor unit. See the instruction manual attached with the outdoor unit for details.
Supplementary refrigerant
The refrigerant supplementation shall be as specified in the installation instructions attached with the outdoor unit. The added refrigerant shall be R22.
The adding procedure shall be aided with a measuring meter for a specified amount of supplemented refrigerant
Requirement
Overfilling or underfilling of refrigerant will cause compressor fault. The amount of the added refrigerant shall be as specified in the instructions.
Pipe cutting and expanding
If the pipe is too long or the flare is damaged, it needs to be cut or expanded.
1. Pipe cutting | 2. Removing burrs | 3.Insertion nut | 4. Pipe expansion |