Pipe and insulation material

Hose Instructions to installation

 

Pipe and insulation material

 

 

Pipe

Rigid PVC pipe VP31.5mm (internal diameter)

 

 

Insulation

Foamed PE with thickness above 7mm

 

 

 

 

 

Hose

Drain pipe size: ÿ19.05mm2 (3/4") PVC pipe.

The hose is used for adjusting the off-center and angle of the rigid PVC pipe.

Directly stretch the hose to install without making any deformation.

The soft end of the hose must be fastened with a hose clamp.

 

Please apply the hose on horizontal part

Hose

 

Insulation treatment:

Wrap the hose and its clamp until to the indoor unit without any clearance with insulating material, as shown in the figure.

Subsidiary insulation

Hose clamp

Insulation

Rigid PVC pipe

Drain confirmation

During trial run, check that there is no leakage at the pipe connection part during water draining even in winter.

Allowable pipe length and drop

These parameters differ according to the outdoor unit. See the instruction manual attached with the outdoor unit for details.

Supplementary refrigerant

The refrigerant supplementation shall be as specified in the installation instructions attached with the outdoor unit. The added refrigerant shall be R22.

The adding procedure shall be aided with a measuring meter for a specified amount of supplemented refrigerant

Requirement

Overfilling or underfilling of refrigerant will cause compressor fault. The amount of the added refrigerant shall be as specified in the instructions.

Pipe cutting and expanding

If the pipe is too long or the flare is damaged, it needs to be cut or expanded.

1. Pipe cutting

2. Removing burrs

3.Insertion nut

4. Pipe expansion

19

Page 21
Image 21
Haier AD142XLERA Instructions to installation, Pipe and insulation material, Hose, Insulation treatment, Requirement