 Failure code

Manual background Failure code

 

TROUBLE SHOOTING

FAILURE CODE

POSSIBLE REASONS

 

(indoor unit)

(CHECK THE WIRED

 

REMOTE CONTROLLER)

 

 

 

 

 

Abnormal communication

 

 

Wrong connection, or use the wired controller

 

between wired controller and

07

*

 

be disconnected, faulty PCB

 

indoor unit PCB

 

 

 

 

Drainage system abnormal

08

*

The short-connector disconnected, or at wrong

 

position, or the float switch broken down or the

 

 

 

float switch disconnected,or at wrong position

 

 

 

 

 

 

Indoor unit address repeated

09

 

Wrong setting of indoor unit address

 

 

 

 

 

 

Abnormal communication

0E

 

Faulty indoor unit PCB

 

between chip TMP/807 and chip

 

 

TMP/846

 

 

 

 

TROUBLE SHOOTING

FAILURE CODE

POSSIBLE REASONS

 

(CHECK THE WIRED

 

(ourdoor unit)

 

REMOTE CONTROLLER)

 

 

 

 

 

 

 

 

 

 

Faulty defrost sensor Te

14

*

Sensor disconnected, or broken, or short circuit

 

 

Sensor disconnected, or broken, or short circuit

 

Faulty sensor Tao

15

 

 

*

 

 

Faulty sensor Ts

 

Sensor disconnected, or broken, or short circuit

 

16

*

 

 

 

 

Faulty sensor Td

17

Sensor disconnected, or broken, or short circuit

 

 

*

Over current of the system, or broken of the

 

Input overcurrent

19

 

 

current sensor,or malfunction with indoor or

 

 

 

 

outdoor fan motors, or faulty PCB.

 

 

 

 

 

 

 

 

 

High pressure switch is disconnected, or high

 

System high pressure

1E

*

pressure switch worked, or Tc too high and

 

faulty outdoor fan motor when cooling, or

 

protection

 

 

faulty indoor fan motors when heating, or

 

 

 

 

 

 

 

 

refrigerant overabundance

 

 

 

 

Low pressure switch is disconnected, or low

 

System low pressure

1F

*

pressure switch worked, or Te too low and

 

faulty outdoor fan motors when heating, or

 

protection

 

 

faulty indoor fan motor when cooling, or

 

 

 

 

 

 

 

 

refrigerant shortage

 

 

 

 

 

 

IPM protection

20

 

IPM over current, or short circuit, or IPM

 

 

temperature too high, or IPM input voltage

 

 

 

 

too low,or faulty SPDU(or ISPM).

 

EEPROM fault

21

 

Faulty outdoor unit PCB

 

 

 

 

 

 

 

 

 

 

Over hot protection of

 

 

Serious lack of refrigerant of the system, or

 

22

 

the ambient temperature too high, or PMVs be

 

compressor

 

 

 

 

blocked

 

 

 

 

 

 

 

 

 

 

Over hot protection of SPDU

23

 

Ambient tempreatrue too high, or outdoor fan

 

(or ISPM)

 

be blocked, or bad air circulation of outdoor unit

 

 

 

 

 

 

DC fan motor fault

24

 

Fan is blocked, or the terminal is disconnected

 

 

 

 

from the PCB

 

 

 

 

 

24