TABLE CONTINUED FROM PAGE 4

TABLE CONTINUED FROM PAGE 4

SINGLE CIRCUIT

DUAL CIRCUIT

 

 

 

3

1

2

2

3

 

1

2

2

 

 

 

 

Maximum

 

 

Minimum

Maximum

 

 

 

 

 

 

 

 

Field

 

External Fuse

Field Power

Ground

 

 

No.

Minimum

External

Ground

Circuit

or

Circuit

 

Rated

Field

Fuse or

Power

Ampacity

Breaker

Wire Size

Wire Size

 

Volts &

Power

Circuit

Circuit

Wire

Wire

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

Phase

Circuits

Ampacity

Breaker

Size

Size

CKT A

CKT B

CKT A

CKT B

CKT A

CKT B

CKT A

CKT B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WA602-A00, A0Z

 

1

44

60

8

10

N/A

N/A

N/A

 

N/A

N/A

N/A

N/A

N/A

A05

 

1

44

60

8

10

N/A

N/A

N/A

 

N/A

N/A

N/A

N/A

N/A

A10

230/208-1

1

55

60

6

10

N/A

N/A

N/A

 

N/A

N/A

N/A

N/A

N/A

A15

 

1 or 2

85

90

4

8

59

26

60

 

30

6

10

10

10

A20

 

1 or 2

110

110

2

6

59

52

60

 

60

6

6

10

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WA602-B00, B0Z

 

1

32

45

8

10

N/A

N/A

N/A

 

N/A

N/A

N/A

N/A

N/A

B09

230/208-3

1

34

45

8

10

N/A

N/A

N/A

 

N/A

N/A

N/A

N/A

N/A

B15

1

52

60

6

10

N/A

N/A

N/A

 

N/A

N/A

N/A

N/A

N/A

B18

 

1

60

60

6

10

N/A

N/A

N/A

 

N/A

N/A

N/A

N/A

N/A

WA602-C00, C0Z

 

1

16

20

12

12

N/A

N/A

N/A

 

N/A

N/A

N/A

N/A

N/A

C09

460-3

1

17

20

12

12

N/A

N/A

N/A

 

N/A

N/A

N/A

N/A

N/A

C15

 

1

26

30

10

10

N/A

N/A

N/A

 

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

jMaximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.

kBased on 75° C copper wire. All wiring must conform to NEC and all local codes.

lThese “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest revision), article 310 for power conductor sizing. CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3 conductors are in a raceway.

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.

GENERAL

The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.

The refrigerant system is completely assembled and charged. All internal wiring is complete.

The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.

These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.

These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.

While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 1 for information on codes and standards.

Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.

Manual 2100-398 Page 5