COMPRESSOR CONTROL MODULE

The compressor control module is standard on the WL484 and WL602 models covered by this manual and is optional on the WL423 model. The compressor control is an anti-short cycle/lockout timer with high and low pressure switch monitoring and alarm relay output.

Adjustable Delay On Make And Break Timer

On initial power up or any time power is interrupted to the unit the delay on make period begins which will be 2 minutes plus 10% of the delay on break setting.

When the delay on make is complete and the high pressure switch (and low pressure switch if employed) is closed, the compressor contactor is energized. Upon shutdown the delay or break timer starts and prevents restart until the delay on break and delay on make periods have expired.

During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor contactor will de-energize immediately. The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay on break time has expired. If the high pressure switch opens again in this same operating cycle the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.

Low Pressure Switch, Bypass, and Lockout Sequence

If the low pressure switch opens for more than 120 seconds, the compressor contactor will de-energize and go into a soft lockout. Regardless the state of the low pressure switch, the contactor will reenergize after the delay on make time delay has expired. If the low pressure switch remains open, or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications where alarm relay is employed. This terminal is powered whenever compressor is locked out due to HPC or LPC sequences as described.

NOTE: Both high and low pressure switch controls are inherently automatic reset devices. The high pressure switch and low pressure switch cut out and cut in settings are fixed by specific air conditioner or heat pump unit model. The lockout features, both soft and manual, are a function of the Compressor Control Module.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break Timer

The potentiometer is used to select Delay on Break time from 30 seconds to 5 minutes. Delay on Make (DOM) timing on power-up and after power interruptions is equal to 2 minutes plus 10% of Delay on Break (DOB) setting:

0.5 minute

(30 seconds) DOB = 123

second DOM

1.0 minute

(60 seconds) DOB = 126

second DOM

2.0minute (120 seconds) DOB = 132 second DOM

3.0minute (180 seconds) DOB = 138 second DOM

4.0minute (240 seconds) DOB = 144 second DOM

5.0minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay.

Typical Settings for Dual Unit Installation:

Unit 1: DOB set at 2 minutes, and DOM is 132 seconds

Unit 2: DOB set at 4 minutes, and DOM is 144 seconds

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all units so that the system operating pressures can be observed. A pressure table can be found later in the manual covering all models. It is imperative to match the correct pressure table to the unit by model number.

Manual 2100-400 Page 15

Page 17
Image 17
Bard WL602, WL423, WL484 installation instructions Compressor Control Module, Pressure Service Ports

WL423, WL602, WL484 specifications

Bard WL484, WL602, and WL423 are part of Bard's innovative line of heating, ventilation, and air conditioning (HVAC) products designed to meet the diverse needs of residential and commercial spaces. Each model is characterized by advanced technologies that enhance energy efficiency, performance, and user comfort.

The Bard WL484 model showcases a heating capacity of 48,000 BTU and operates efficiently in various environments. This unit incorporates a robust heat exchanger, which allows for rapid heating without sacrificing efficiency. One of the standout features of the WL484 is its integrated control system that allows users to set precise temperatures, enhancing comfort while minimizing energy usage. Additionally, this model is designed with superior airflow capabilities, providing even temperature distribution throughout the space it serves.

The Bard WL602, with a heating capacity of 60,000 BTU, emphasizes versatility and performance. This unit is equipped with a multi-speed blower that adjusts the airflow according to the specific heating requirements of the environment. The WL602 is engineered with a durable cabinet that resists corrosion, ensuring longevity and reduced maintenance needs. It also includes advanced diagnostic capabilities, allowing users to identify issues quickly and streamline servicing. With its enhanced efficiency ratings, the WL602 is a solid choice for larger spaces requiring reliable and economic heating solutions.

The Bard WL423 model serves as an efficient option for smaller spaces with a heating capacity of 24,000 BTU. This compact unit is designed to fit into tighter spaces while delivering exceptional performance. One unique characteristic of the WL423 is its quiet operation, making it suitable for environments where noise levels must be kept to a minimum, such as offices or bedrooms. Additionally, it features energy-efficient components that help reduce operating costs over time, making it an attractive option for budget-conscious consumers.

In summary, Bard WL484, WL602, and WL423 each bring distinct advantages to the HVAC market, with features designed for optimal performance, energy efficiency, and user satisfaction. These models represent Bard's commitment to quality and innovation, ensuring that customers can find the right solution for their specific heating needs. Whether for residential or commercial applications, Bard continues to be a trusted name in climate control technology.