Beckett 7559 Features, Specifications, Electrical Ratings, Environmental Ratings, Result, Inputs

Models: 7559

1 8
Download 8 pages 8.75 Kb
Page 2
Image 2
Features

Features

Welded Relay Protection

Limited Relight

Valve-On Delay / Motor-Off Delay (Field programmable with Beckett’s Contractor Tool)

15 Second Lockout Time

Interrupted Ignition

Communication Port

Lockout Alarm Output

Fused Protection

Specifications

 

Do Not Use This Control

CAUTION

in an Application that

is Not Within the Ratings Listed in This

Section. Improper Control Operation May

Result.

 

 

 

 

Do Not Use This Control

CAUTION

 

Above 5.5 GPH

 

Electrical Ratings

Inputs:

Voltage: 24 Vdc nominal (21.6 to 30 Vdc)

Current: 220 mA nominal (230 mA max at 30 Vdc)*

Enable Load: 22mA at 24 Vdc

Outputs:

Motor: 24 Vdc, 10 full load amps (FLA), 50 locked rotor amps (LRA)

Igniter: 24 Vdc, 3 A

Solenoid Valve: 24 Vdc, 1 A

Lockout Alarm: 24 Vdc, 1A

*

 

The 7559 control draws

￿￿￿￿￿￿

 

 

40-55mA in the standby

 

 

state. If the red control wire is left powered without a battery charging system, it can drain a standard 45 Amp hour automotive battery in four to six weeks.

Environmental Ratings:

Storage and Operating Ambient Temperature: -40°F to +160°F (-40°C to +71°C)

Moisture: 5 to 95% RH, condensing

SpecificationsWARNING MaintainVoltage Specified

A low or erratic power supply could result in impaired burner operation, severe delayed ignition or an explosion inside the heat exchanger resulting in a burn and/or asphyxiation hazard.

yBeckett DC Burners require a continuous supply of 21.6 to 30 volts DC (at 11 amps for Model ADC or 15 amps for Model SDC), measured at the burner during operation.

yConsult other DC burner manufacturers’ specifications for the correct voltage range.

ySpecial Note: The 7559 Control shuts the burner down if the input voltage drops to a sustained level of 20 volts DC, or below. Operation resumes at a sustained input voltage of 21 volts DC, or above.

yAn automotive or small engine charging system that is capable of supplying the required continuous voltage/amperage is recommended with certain road equipment, such as asphalt hot patchers and similar applications.

yThis is especially true while maintaining nominal load temperatures during idle periods.

Table 1 - Model Guide

Beckett

 

Valve-on
Motor-
GeniSys
Lockout

off

delay
24V Control

Time

delay

time1

Part No.

 

time1

7559A 0000 1

15 sec

0 sec

0 sec

 

 

 

 

7559P 1530 1

15 sec

15 sec

30 sec

7559P 152M 1

15 sec

15 sec

2 min

 

 

 

 

7559P 158M 1

15 sec

15 sec

8 min

 

 

 

 

1Valve-on delay and motor-off delay timings on all models are programmable with the Beckett Contractor Tool. Other factory set timings are available. Contact Beckett for alternate timings.