Instruction Manual – Model AFG Oil Burner

Startup & adjust burner

Service & maintain burner

Startup burner/set combustion

Do not attempt to start the burner when excess fuel or vapor has accumulated in the appliance. Starting the burner under these conditions could result in a puffback of hot combustion gases, high smoke levels, or otherwise hazardous operation.

1.Open the shutoff valves in the oil supply line to the burner.

2.Close air band and partially open air shutter. This is an initial air setting for the pump venting procedure only.￿Additional adjustments must be made with instruments.

3.Set the thermostat substantially above room temperature.

4.Close the line voltage switch to start the burner. If the burner does not start immediately you may have to reset the safety switch of the burner primary control.

5.￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿as soon as burner motor starts rotating.

To vent the fuel unit, attach a clear plastic hose over the vent plug. Loosen the plug and catch the oil in an empty container. Tighten the plug when all air has been purged from the oil supply system.

If the burner locks out on safety during venting, reset the safety switch and complete the venting procedure. Note — Electronic safety switches can be reset immediately; others may require a three- to five-minute wait.

If burner stops after flame is established, additional venting is probably required. Repeat the venting procedure until the pump is primed and a flame is established when the vent plug is closed.

For R7184 primary controls, see Technician’s Quick Reference Guide, Beckett part number 61351, for special pump priming sequence.

Prepare for combustion tests by drilling a ¼" sampling hole in the flue pipe between the appliance and the barometric draft regulator.

6.￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿— Using a smoke tester, adjust the air shutter (and air band, if necessary) to obtain a clean flame. Now the additional combustion tests with instruments can be made.

Set combustion with instruments

The combustion must be adjusted using test instruments. Failure to do so could result in burner or appliance failure, causing potential severe personal injury, death or substantial property damage.

1.Let burner run for approximately 5 to 10 minutes.

2.Set the over-fire or stack draft to level specified by appliance manufacturer (usually –0.01 to –0.02 inches w.c. over-fire for natural draft applications).

3.Follow these four steps to properly adjust the burner: Step 1: Adjust air until a trace smoke level is achieved.

Step 2: At the trace of smoke level, measure the CO2 (or O2). This is the vital reference point for further adjustments.

• Example: 13.5% CO2 (2.6% O2).

Step 3: Increase the air to reduce CO2 by 1 to 2 percentage points. (O2 will be increased by approximately 1.4 to 2.7 percentage points.)

Example: Reduce CO2 from 13.5% to 11.5%. (O2 — 2.6% to 5.3%.) Step 4: Recheck smoke level. It should be zero.

This procedure provides a margin of reserve air to accommodate vari- able conditions.

If the draft level has to be changed, recheck the smoke and CO2 levels. Adjust the burner air if necessary.

4.Once combustion is set, tighten all fasteners on air band, air shutter and head adjusting plate or escutcheon plate.

5.Burner equipped with cover — Reinstall cover and repeat steps 2 and 4

above. If CO2 increases (O2 decreases), remove the cover and adjust the air setting so the CO2 (O2) with cover on meets the requirements of step 3.

6.Start and stop the burner several times to ensure satisfactory operation. Test the primary control and all other appliance safety controls to verify that they function according to the manufacturer’s specifications.

Perform annual maintenance

This equipment must be serviced only by a qualified service agency. The appropriate test instruments must be used. Failure to do so could result in burner or appliance failure, causing potential severe personal injury, death or sub- stantial property damage.

Replace the oil supply line filter. The line filter cartridge must be replaced to avoid contamination of the fuel unit and nozzle.

Inspect the oil supply system. All fittings should be leak-tight. The supply lines should be free of water, sludge and other restrictions.

Remove and clean the pump strainer if applicable.

Replace the nozzle with an equivalent nozzle.

Clean and inspect the electrodes for damage, replacing any that are cracked or chipped.

Check electrode tip settings. Replace electrodes if tips are rounded.

Inspect the igniter spring contacts.

Clean the cad cell grid surface, if necessary.

Make sure low firing rate baffle is in place if required for the burner applica- tion. Omitting the baffle can result in unacceptable burner combustion.

Inspect all gaskets. Replace any that are damaged or would fail to seal adequately.

Clean the blower wheel, air inlet, air guide, retention head and static plate of any lint or foreign material.

If motor is not permanently lubricated, oil motor with a few drops of SAE 20 nondetergent oil at each oil hole. DO NOT over oil motor. Excessive oiling can cause motor failure.

Check motor current. The Amp draw should not exceed the nameplate rating by more than 10%.

Check all wiring for secure connections or insulation breaks.

Check the pump pressure and cutoff function.

Check primary control safety lockout timing.

Check ignition system for proper operation.

Inspect the vent system and chimney for soot accumulation or other restric- tion.

Clean the appliance thoroughly according to the manufacturer's recommen- dations.

Check the burner performance. Refer to the section “Set combustion with instruments.”

It is good practice to make a record of the service performed and the combustion test results.

To replace blower wheel:

1.Turn off all power to the burner before servicing.

2.Disconnect the wires to the burner mo- tor.

3.Remove the bolts securing the blower motor to the housing.

4.Remove the blower motor and wheel.

5.Remove the existing wheel.

6.As shown at right, slide the new blower wheel onto the shaft.

Place a .030" (1/32" ± 1/64") feeler gauge on the motor as shown.

Slide blower wheel toward motor until it contacts feeler gauge.

Rotate the wheel until the set screw

is centered on the flat of the motor shaft.

• Tighten the set screw to secure the wheel.

7.DO NOT use a motor that has endshield openings outside the blower wheel circumference represented by the dashed line.

8.Install the motor on the burner housing. Tighten screws. Reconnect motor wires.

9.Restore power, start the burner and perform combustion tests. Refer to “Set combustion with instruments￿

10

Page 10
Image 10
Beckett AFG Oil Burner Startup burner/set combustion, Perform annual maintenance, To replace blower wheel

AFG Oil Burner specifications

The Beckett AFG Oil Burner stands as a top choice for residential and commercial heating applications, recognized for its reliability, efficiency, and innovation. Engineered to deliver optimal performance, this burner has become a market favorite among HVAC professionals and homeowners alike.

One of the standout features of the AFG Oil Burner is its advanced technology for efficient fuel combustion. The burner employs a unique air-fuel ratio control system, which ensures precise mixing of air and oil for maximum efficiency. This not only enhances heating performance but also contributes to significant fuel savings, making it an environmentally friendly option.

The Beckett AFG is designed with a compact, lightweight structure, facilitating easy installation and maintenance. Its proprietary design minimizes noise levels during operation, providing a quiet heating solution ideal for residential settings. The burner also features an automatic reset capability, which enhances safety by shutting off in the case of an operational fault, thus preventing potential hazards.

Another noteworthy characteristic of the AFG Oil Burner is its versatile application range. It supports various oil types, including No. 1 and No. 2 fuel oils, making it suitable for different heating requirements. The burner’s adaptability extends to various applications, including forced hot air, hot water boilers, and steam systems.

In terms of performance, the AFG model boasts impressive firing rates, providing up to 3.5 GPH, suitable for both small homes and larger commercial establishments. Its ability to maintain consistent fuel flow helps reduce wear and tear on the heating system, extending its longevity.

The user-friendly feature of the Beckett AFG includes an advanced ignition system that ensures quick and reliable startups. This system dramatically decreases the risk of ignition failures, providing peace of mind for users.

Furthermore, Beckett's commitment to quality is evident in the robust construction of the AFG Oil Burner. Made from high-grade materials, this burner is built to withstand the rigors of frequent operation.

In summary, the Beckett AFG Oil Burner is a high-performance, energy-efficient solution that combines advanced technology, safety features, and versatile applications. Its dependability and efficiency make it an excellent investment for anyone seeking effective heating solutions.