Beckett CF3500 specifications Overall Dimensions, Typical Burner Sequence of Operation, Features

Models: CF3500

1 2
Download 2 pages 38.59 Kb
Page 1
Image 1
BECKETT

BECKETT

CF3500

COMMERCIAL OIL BURNER

Overall Dimensions

22.5

CF3500Overall Dimensions12.722.5

28.0 Min.

28.0 Min. 39.0 Max. 5.3

7.88

8.00

5.3

14.7

Typical Burner Sequence of Operation - 7505

1

Standby

9

Pump

Prime

Specifications

2 Valve-on

3

Trial for

4

Fuels

Firing Range Motor

U.S. #1 or #2 heating oil only (ASTM D396) Canada #1 stove oil or #2 furnace oil only

DO NOT USE

GASOLINE, CRANKCASE OIL, OR ANY OIL CONTAINING GASOLINE.

17.0 to 35.0 gph

2 HP 3450 rpm 208/230/60 Hz Standard 13.4 amps @ 230 VAC

Delay

Typical Burner Sequence of Operation - 75058 Motor-off Delay

Ignition

5Specifications Ignition Carryover

6

Run

Lockout

7

Recycle

Ignition Trans.

Housing

Fuel Unit

Oil Nozzle

Optional Voltages:

208, 230, 480, 575 VAC/3-PH, 50 or 60 Hz

Continuous Duty, 120V/12,000V

Cast aluminum

100 to 300 psig

45o to 70o Solid

Two-pipe Oil Flow

200 - 300

PSIG

Features

S - Standard

O - Optional

N/A - Not Available

 

On/Off

 

 

N/A

Linkageless Low/High/Low or Low/High/Off

 

S

Air Proving Switch

 

 

S

Direct Spark Ignition of Main Flame

 

S

Flame Safeguard with UV Sensor or Light Sensor

O

Customized Electrical Cabinet

 

O

UL/CUL - CSD1 - XL GAPS 1

 

S

FM

 

 

O

IRI (old standard)

 

 

O

200 - 300

PSIG

www.beckettcorp.com

R.W. Beckett Corporation ● Elyria, Ohio

Page 1
Image 1