
Appliance details
The maximum flue gas exhaust temperature on the 2400 E is 437°F (225°C)
Venting | Exhaust | * Exhaust | * Exhaust | Combustion | Combustion | Vent pipe | Vent pipe |
Options | vent | vent | vent | air pipe | air pipe | clearances | clearances |
| diameter | maximum | minimum | diameter | maximum | within an | within an |
| and | length | length | and material | length | unenclosed | enclosed |
| material |
|
|
|
| space | space |
|
|
|
|
|
|
|
|
Room | 3 or 4+ | 26 feet (8 | 3 feet | 3 inch PVC, | 26 feet (8 | ** See vent | ** See vent |
sealed | inch | m) with one |
| aluminum or | m) with one | manufacturer's | manufacturer's |
(twin pipe) | stainless | elbow. Less |
| galvanized | elbow. Less | specifications | specifications |
| steel | 2½ feet for |
| pipe | 2½ feet for |
|
|
| each |
|
| each |
|
| |
| sealed vent | additional |
|
| additional |
|
|
| pipe | 90° elbow |
|
| 90° elbow |
|
|
Open | 3 or 4+ | 26 feet (8 | 3 feet | See | See | ** See vent | ** See vent |
combustion | inch | m) with one |
| chapter 2.8 | chapter 2.8 | manufacturer's | manufacturer's |
(single | stainless | elbow. Less |
|
|
| specifications | specifications |
pipe) | steel | 2½ feet for |
|
|
|
|
|
| each |
|
|
|
|
| |
| sealed vent | additional |
|
|
|
|
|
| pipe | 90° elbow |
|
|
|
|
|
|
|
|
|
|
|
|
|
Exhaust vent is always fan assisted. Installation of exhaust vent and combustion air piping may be run vertically or horizontally and in separate directions if required.
+The exhaust collar on the water heater is 3" diameter and its collar must always be used, a 3" to 4" increaser will be required to be first connected to the exhaust collar when 4" venting is used.
* A maximum of three 90 degree elbows are permitted in both the exhaust and combustion air vent lengths. The total vent length must be reduced by 1 ¼ feet for every 45° elbow used in the vent system.
** Stainless steel
Table 3
The appliance should be located as close to the point of termination as possible. The maximum vent length is 26 feet (8 m) with one 90 degree elbow. Subtract 2½ feet from the total vent length for each additional 90° elbow used (a maximum of three 90° elbows are permitted in the total vent length), or subtract 1 ¼ feet for every 45° elbow used. Horizontal sections of vent must pitch ¼" for every foot of horizontal length, to prevent the pooling of condensate, and be supported at 4 foot intervals with overhead hangers.
Note: Listed thimbles or collars are necessary to pass through wall and ceiling partitions. If the vent system passes through combustible areas where the vent clearance requirements cannot be maintained, it is permissible to chase straight sections of sealed 3 inch single wall vent through 4 inch (or greater)
The minimum exhaust vent length is 3 feet.
The use of a 90 degree elbow is equivalent to 2 ½ ft in vent length. The use of 45 degree elbow is equivalent to 1 ¼ ft in vent length.
Fig. 7
Maximum exhaust vent and combustion air inlet lengthsFig. 8
10 | 6 720 608 263 |