9.0 Application Tips
When using photoelectric detectors for motion detection, there are a few installation techniques that will make the system more versatile.
9.2 Perimeter Protection
When protecting the interior of an installation, a good technique is to mount the units at 90° angles around the coverage area (see Figure R).
9.1 Beam Stacking
Beam stacking gives a wall of protection by stacking several units at different heights and providing an alarm activation on the blockage of only one pair of beams (see Figure N for the correct
T1 | R1 |
S |
|
R2 | T2 |
| D |
Figure N - Beam stack method
R4 | T2 |
T1 | R1 |
R3 | T3 |
The maximum spacing between receivers (S) can be calculated by dividing the distance between the transmitter and its receivers (D) by 20.
Therefore, if the distance between a transmitter and receiver is 100 ft. (30 m), the maximum spacing between receivers would be 100 ft. (30 m) ÷ 20, or 5 ft. (1.5 m)
S = D/20 S = 100 ft. (30 m)/20 S = 5 ft. (1.5 m)
A potential problem when installing systems in a beam stack is “Near Field Reflection.” Near field reflection is caused when a reflective object is placed in the
T4 | R2 |
Figure R- Perimeter protection
Note that the beams are mounted so they cross each other. This way, an intruder can not enter the area by walking between the units. When installing multiple transmitters and receivers, test with all the receivers
Receivers physically too close to a different system’s transmitters may be set up even if the transmitter is not pointed at them (see Figure T).
T1 | R1 |
|
R2 | T2 |
|
Figure P - Near field reflection
It may be desirable to have more than two sets of beams to create taller stacks. This can be accomplished by adding receivers as shown in Figure Q). Note that the beam from each transmitter is covering two receivers.
T1 | R1 |
R3 | R2 |
R4 | T2 |
Figure T - Close proximity field problem
If a receiver is being set up by the wrong transmitter, the signals can usually be eliminated by masking the sides of the transmitter and receiver. Use electrician’s tape or duct tape inside each enclosure’s window.
When installing these systems, remember that the infrared signal may reflect off objects (e.g. glossy walls or floors) in the coverage area and still set up the receiver.
A thorough walk test performed at several different points within the coverage area will catch this problem.
The only way to insure proper continual protection is to perform regular walk tests of the desired coverage area.
Figure Q - Multi-system stack
© 2004 Bosch Security Systems | 03/04 |
130 Perinton Parkway, Fairport, New York, USA | DS422i/DS426i Installation Instructions |
Customer Service: (800) | P/N: 44974D Page 4 |