2 FMC‑210‑SM Single Action Call Points
•The maximum number of LSN elements that may be connected depends on their current consumption from the LSN data line. The limit values should be taken from the product information supplied with the fire panel used.
•Further standards, guidelines and planning recommendations regarding the installation location etc., should also be taken into consideration (see Fire Detection manual).
•The regulations of the local fire services must be observed.
Installation notes in accordance with VdS/VDE
•The distance between manual call points should not be more than 100 m according to DIN 14675 or 80 m according to VdS.
•In high risk areas, manual call points should be installed at a distance of max. 40 m (VDE 0833 Part 2, Point 7.2.6).
Installation
•The cable duct can be
1
135 mm |
2,5 mm
2 |
140 mm |
2 mm | 12,5 mm |
3 |
|
149,5 mm
mm139
•Installation in fire hose cabinets is possible in three ways:
Pos. Description
1Installation depth version 1: ca. 40 mm
2Installation depth version 2: 14 mm
3Installation depth version 3: min. 30 mm
Parts Included
TypeNumber. |
| Component |
FMC‑210‑SM‑G‑B | Single Action Call Point for indoor use, direct trig- | |
Form G, Blue |
| gering (type A) |
FMC‑210‑SM‑G‑R | Single Action Call Point for indoor use, direct trig- | |
Form G, Red |
| gering (type A |
Note | The key must be ordered separately. |
Technical Specifications
Electrical
Operating voltage | 15 V DC . . . 33 V DC | |
Current consumption | 0.4 mA | |
Mechanics |
| |
Dimensions (H x W x D) | 135 x 135 x 40 mm | |
Housing material | Plastic, ASA | |
Colors |
|
|
• | Red, RAL 3001 | |
• | Blue, RAL 5005 |
Weight | Approx. 235 g |