Fire Alarm Systems FMC‑210‑SM Single Action Call Points
FMC‑210‑SM Single Action Call Points
The FMC‑210‑SM Single Action Call Points are used for manual triggering, and can be used in the Local SecurityNetwork LSN and LSN improved. The FMC‑210‑SM Single Action Call Points are designed for indoor deployment.
▶Alarm triggering by breaking of the glass pane
▶Automatic or manual detector addressing via rotary switch possible
▶Indicator LED for alarm or for inspection evaluation
▶Call point query routines with evaluation and multiple transmission
▶Individual call point identification
▶Maintains LSN loop functions in the event of wire interruption or
Individual call point identification with display of the call point address on the fire panel ensures the quick location of the triggered call point.
Functions
5
1 | 1 |
2
4
3
32
With single action call points, the alarm is triggered when the glass plate (2) is broken and the button (3) springs up.
This activates the microswitch for alarm triggering and the indicator LED (4) blinks.
The call point (3) can be reset after inserting a new glass pane (2) and closing the door of the single action call point (1). The indicator LED (4) goes out.
This does not reset the alarm on the fire panel.
Certifications and Approvals
FMC‑210‑SM‑G‑R applies to
•EN 54‑11:2001/A1:2005
•EN 54‑17:2005
Region | Certification |
|
Germany | VdS | G 207008 |
Europe | CPD |
Installation/Configuration Notes
•Manual call points must be mounted visibly along escape and rescue routes (e. g. exits, passageways, stairwells) and be easily accessible.
•An installation height of 1400 mm ±200 mm, measured from the middle of the manual call point to the floor, must be maintained.
•Manual call points must be adequately illuminated by sunlight or another light source (including emergency lighting if present).