3 FPA‑1000 Analog Addressable Fire Panels
On-board Relays
Three programmable
Option Bus
On the Option Bus, the FPA-1000 supports:
•up to eight
•up to eight D7030X Series LED Annunciators with eight LED zones each,
•up to eight D7030X Series/D7032 combinations
•up to two Octal Relay Modules or Octal Driver Modules
•up to four FPP‑RNAC‑8A‑4C Remote Notification Appliance Circuit Power Supplies.
The outputs of the Octal Relay Modules or Octal Driver Modules are fully programmable, and can be activated by system events. These outputs have the same programming options as the local relays. Each output operates independently of the other seven to provide complete flexibility. Communication with the D7035/B or D7048/B is supervised.
Power
A transformer working with 120 VAC or 240 VAC is supplied standard with the control panel. Two backup batteries with 7 Ah to 18 Ah each fit inside the fire panel cabinet. A separate battery box can provide higher capacity. An automated battery calculator sheet is available online to aid in battery selection and submittal paperwork.
The
For installations requiring battery capacity higher than 40 Ah, a regulated and UL1481 Listed external power supply can be used. The external power supply connects through the panel's battery terminals and is supervised for AC and battery fault by an input module on the SLC.
The
Signaling Line Circuits (SLCs)
The FPA‑1000 Fire Panels communicate with each of the analog addressable devices located on the SLCs. The SLCs allow the use of standard non‑twisted, non‑shielded wiring. Each panel supports two Class B, Style 4 or one Class A, Style 6 or 7 per SLC.
Certifications and Approvals
Region | Certification | |
|
|
|
USA | UL | FSZI.S1871: Emergency Alarm System |
|
| Control Units (ANSI/UL 2017); UOJZ: |
|
| Control Units, System (ANSI/UL 864) |
| CSFM | |
| FDNY- | #6101 |
| CoA |
|
|
|
|
Installation/Configuration Notes
Mounting Considerations
The cabinet can be either
Depending on the configuration and the battery selection, the FPA‑1000 can be quite heavy. When attaching the enclosure to a surface, use mounting hardware (not supplied) capable of supporting this weight, and reinforce the wall as necessary.
Wiring Considerations
The length of wire allowed between the control panel and the last device on a wiring run depends on the current drawn on that wiring run. Reducing the number of devices on a wiring run allows the individual runs to be longer.
If not otherwise specified, use wire gauge 12 AWG to 18 AWG (3.3 mm2 to 0.8 mm2).
Notice
Shared cable is not recommended for the Option Bus, addressable‑points bus, telephone, or NAC wiring. Do not run wiring for NAC, Option Bus, and SLC in the same conduit. Avoid shielded or
Point Capacity/Configuration
Each