Fire Alarm Systems FPA1000 Analog Addressable Fire Panels

FPA1000 Analog Addressable Fire Panels

www.boschsecurity.com

The FPA1000 Analog Addressable Fire Panels are a scalable solution for fire detection. Protect your small office with a single system or connect multiple panels together as your needs grow. Networking capabilities support the monitoring of up to 2,000 addressable points in one system for campuses or other large commercial environments.

The FPA1000 panels combine complete built-in Fire Alarm Control Panel (FACP) equipment such as Notification Appliance Circuits (NACs), Signaling Line Circuits (SLCs), relays, power supply, Digital Alarm Communicator Transmitter (DACT), and Ethernet connection with expandability using the option bus or plugin boards. The two integrated NACs can be expanded with remote addressable NAC power boosters and programmed with specific activation patterns.

The standard control panel includes one SLC that supports 254 addressable points (254 analog detectors or modules, or 127 analog sounder bases in combination with a suitable detector). The control panel is easily expandable with the FPE1000SLC Signaling Line Circuit Plug-in Module, doubling the address points to 508.

uSupport for up to 508 points on two analog addressable loops

uBuilt-in Ethernet connector for web-browser based programming and Conettix Alarm-over-IP communication

uTwo on-board NACs and dual-line PSTN DACT

uPeer-to-peer networking of up to eight panels in a single group

uSimple system management and free online training

The panel has a compact and solid metal housing with a keyed lock and a removable dead front door to access electronics. It features surface and semi-flush mounting options. On the front of the panel, six light- emitting diodes (LEDs) show Fire, Carbon Monoxide (Gas) Alarm, Power, Supervisory, Silenced, and Trouble conditions. The builtin keypad can be used for total system control and programming even when wearing fireman gloves. In addition, a large 4line by 20character alphanumeric LCD display shows programmed device point information. Four keys enable Drill, Reset, Silence, and Acknowledge functions.

The FPA1000 panels enable various programming approaches:

Front panel programming

On-site programming, using a laptop with the possibility of pre-programming at the office

Off-site programming, with remote access via Ethernet (browser-based).

Front panel programming provides an autolearn function, allowing the installer to configure the system quickly and easily in default mode. Using a local laptop or remote access communication, the programming is carried out by means of a browserbased user

Page 1
Image 1
Bosch Appliances FPA-1000 manual FPA‑1000 Analog Addressable Fire Panels