Local Energy Mode

The FPE-1000-CITY connects Local Energy signaling devices to the FPA-1000 fire panel for auxiliary service operation.

Refer to the FPA-1000 Installation and Operation Guide for a listing of compatible Gamewell devices.

Terminal

 

 

 

ALM - +

Connects to Municipal Master Box

 

 

SUP - +

Not used

ALM-

 

 

 

 

 

 

ALM+

 

 

 

SUP-

 

 

 

SUP+

 

 

 

Figure 4

Local Energy Mode

Specifications

 

 

Circuit resistance

65 Ω

Wire gauge

12 to 18 AWG (3.3 mm2 to 0.8 mm2)

Operating temperature

32 °F to 120 °F (0 °C to 49 °C)

Storage temperature

-4 °F to 140 °F (-20 °C to 60 °C)

Relative humidity

Up to 93%, non-condensing

Reverse Polarity Mode

 

Nominal Voltage

24 V DC nominal (26.4 V DC maximum), power-limited, supervised

Output current

33 mA maximum

Supervisory/standby current

5 mA

Local Energy Mode

 

Type of connection

In series

Alarm, trip coil

24 V DC

Alarm current

250 mA (momentary, <1 ms)

Supervisory/standby current

<50 mA DC

Trip coil resistance

14.5 Ω

Nominal coil voltage

3.65 V DC, power-limited, supervised