FPE-1000-CITYen 5

FPE-1000-CITY

 

S1 = SUP

 

 

S2 = ALM

 

DIP Switches

 

 

 

 

 

 

 

1

2

3

1

2

3

 

 

 

 

 

 

 

Reverse Polarity Mode

ON

ON

ON

ON

ON

ON

Local Energy

OFF

OFF

OFF

OFF

OFF

OFF

Note: You may use different operation modes for the circuits. The DIP switch settings 1 to 3 for each switch (S1 and S2) must be set to the same position.

Mounting

1.Bring the plug-in module into position with the horizontal terminal lettering facing the front side of the control panel. Slide the plug-in module carefully into position along the guide rails (refer to Figure 2, Page 5, Item 1)

2.Ensure that the connections seat into the slot properly (refer to Figure 2, Page 5, Item 2).

3.Press down softly until the snap-fit hook locks into place (refer to Figure 2, Page 5, Item 3).

Fire

 

 

Gas Alarm

Power

1

Supervisory

 

Silenced

Trouble

DRILL

RESET

SILENCE

ACK

2

 

 

 

?

 

 

@ _

 

 

 

 

 

 

 

 

 

 

3

. : ,

A↔a

 

 

 

 

1

Figure 2 Installing the FPE-1000-CITY City Tie Plug-in Module

To remove a plug-in module, press the snap-fit hook carefully from left to right and pull the board toward the panel front.

Wiring

No special wire is required for addressable loops. The wire can be untwisted, unshielded, solid or stranded as long as it meets the National Electric Code 760-51 requirements for power-limited fire protective signaling cables. Observe a maximum circuit resistance of 65 Ω.

Note: Use the appropiate DIP switch setting at the module to obtain the desired operation mode (refer to Figure 1, Page 4).

Reverse Polarity Mode

The FPE-1000-CITY connects the FPA-1000 Analog Addressable Fire Panel to either a single set or a pair of dual leased telephone company (telco) lines in NFPA 72 Remote Station applications. The FPE-1000-CITY relays system alarm status information from the control panel to a monitoring station.

In normal conditions, the FPE-1000-CITY sends a steady current to a monitoring station. In an alarm condition, it reverses the polarity of the output current. The FPE-1000-CITY signals a trouble condition by interrupting the output voltage and current.

The default setting is fire alarm for circuit 1 and supervisory for circuit 2.

NOTICE!

Intended for connection to a polarity reversal circuit of a remote station receiving unit having compatible ratings.

Terminal

Default setting

ALM - +

Fire Alarm

SUP - +

Supervisory

Legend

 

MMonitoring Station

ALM+- M SUP+-

Figure 3 Reverse Polarity Mode

Bosch Security Systems, Inc.

F.01U.078.100 04 2011.11

Page 5
Image 5
Bosch Appliances FPE-1000-CITY manual Wiring