Cabinet requirements | The | distance from the top of the cooktop to the bottom | of cabinets above | ||
| A = | 30" (762 mm) min. This distance can be reduced to A = 24" (610 | |||
| bottom of the wood or metal cabinet | is protected by not | less than 1/4" | ||
| flame | retardant millboard, covered by no. 28 MSG sheet steel, 0.015" (0.4 | |||
| thick | stainless steel, 0.024" (0.6 mm) | aluminum or 0.020" | (0.5 mm) thick c | |
| Verify | that cabinets above the cooktop | are a maximum of | B=13" (330mm) | |
|
|
|
|
|
|
|
|
|
|
|
|
Electrical requiements | You | can find the identification plate with the electrical | specifications | on the | ||
| underside of the appliance. See •Product Data Plate" under •Service" for da | |||||
| location. |
|
|
|
| |
| The | junctionbox must | be | located within 3 feet of the | cooktop connection. I | |
| be | easily accessible | for | service purposes. |
|
|
12" Approximate
•J" Box
(Conduit approx. 3 feet)
Power Supply
Models NIT8653UC 50 Amp circuit breaker 240 Volt, 3 Wire, 60 Hz 208 Volt, 3 Wire, 60 Hz
All with 1m flexible conduit (included)
6