FLM‑I 420‑S Short Circuit Isolator

Fire Alarm Systems FLMI 420S Short Circuit Isolator

FLMI 420S Short Circuit Isolator

Rotary switch for automatic and manual address setting

Preservation of LSN loop functions in the event of a short-circuit by two integrated isolators

Power supply via LSN

Three free screw terminals

The Short Circuit Isolator isolates alarm zones in which a short circuit has occurred. This means the functionality of the remainder of the network remains preserved.

Functions

Features of improved LSN

The interface modules in the 420 series offer all the features of improved LSN technology:

System Overview

CL 0

1

9

0

1

9 0

1

 

2

8

 

2

8

2

 

 

76

5

4 3

76 5

4 3

 

LSN

 

 

 

 

 

b1+

a-

b2+

N/A

N/A

N/A

Description

Connector

b1+ / a- / b2+

LSN

N/A (3 x)

free terminals, e.g. for looping through ext. auxiliary volt-

 

age and for shielding

Flexible network structures including Ttapping without additional elements

Up to 254 LSN-improved elements per loop or stub line

Unshielded cable can be used

Address switch (rotary switch)

The address of the Short Circuit Isolator is set using the rotary switches.

The following settings are possible:

0 0 0

Loop/stub in LSN mode improved version with automatic

 

addressing (T-tap system not possible)

0 0 1 - 254 Loop/stub/T-tap system in LSN mode improved version

 

with manual addressing

CL 0 0

Loop/stub in classic LSN mode

Configuration

The Short Circuit Isolator isolates alarm zones in which a short circuit has occurred. The following illustrations show typical configurations of the isolator module.