10.In the control compartment, find the manual reset high-limit switch box (see Figure 15) and loosen the screw on the top to remove the cover.

11.Loosen the screw that fastens the white wire and remove it from the terminal. Pull it out through the top of the case and separate the other white wire from the red wire coming from the fuse

2-Stage/

OperatingInlet Oulet High Limit Controller

Header

Modulating (if installed)

Figure 17. Sensory bulb locations.

Retaining

Clip

Figure 18. Retaining clip removal.

3.1 in.

(79mm)

 

2.4 in.

0.9 in. dia

 

(61mm)

Attach Capillary

 

(23mm)

 

(Two holes)

Covers on

 

 

 

Left Side

2.4 in.

FRONT

 

(61mm)

1.9 in.

LEFT

(48mm)

 

Figure 19. Hole location, left side.

holder. Gently pull the two white wires out of the control compartment and coil them on top of the heat exchanger.

12.A temperature control sensing bulb is located in the front of the header on the inlet side and a manual reset hi-limit sensing bulb is located on the back side of the header on the outlet side (see Figure 17). Remove these sensing bulbs from the

header. The following steps for removal apply to all sensing bulbs:

a.If there is more than one capillary tube coming out of the header, label the capillary tubes.

b.Loosen the screw on the capillary tube retaining clip, then gently pry the clip apart until it comes free from the temperature control (see Figure 18).

c.Pull the sensing bulbs out of the temperature control.

d.Gently pull the capillary tubes into the control compartment.

e.Pull the temperature sensing bulb out of the header, and temporarily route it to the front of the heater.

13.Use a pair of diagonal cutters to cut the plastic tie around the wire bundle in the control compartment.

14.On the terminal strip, disconnect the two brown wires from No. 5 and No. 6 terminals.

15.Remove the flow switch conduit retaining clip and the elbow leading into the jacket.

16.Reach inside the control compartment and release the retaining nut in the upper right corner. The nut should only be finger-tight.

17.When the conduit is pulled away from the jacket, pull the two brown wires out of the control compartment. Coil the conduit and wires on top of the heat exchanger.

18.Use a chassis punch to put two 7/8 inch (22 mm) holes in the front left side of the jacket (see Figure 19).

19.Remove the front and rear tile covers (see Figure 15).

20.Lift out the heat exchanger assembly, turn it 180 degrees, and reseat the unit in the heater with the water connections on the left side.

21.Reinstall the front and rear tile covers.

22.Push the capillary tube(s) out through the lower hole in the left side of the jacket.

23.Install the sensing bulb(s) into the appropriate temperature control (keep in mind that the positions of the inlet and outlet have been reversed. The inlet is now behind the outlet).

Page 10
Image 10
Bradford-White Corp B4 warranty Front

B4 specifications

Bradford-White Corp B4 is a remarkable water heater that embodies innovation, efficiency, and reliability. This product is designed to meet the stringent demands of both residential and commercial applications, making it a versatile choice for various users.

One of the standout features of the Bradford-White B4 is its high-efficiency operation. With advanced insulation technologies, this water heater minimizes heat loss, allowing it to perform efficiently while conserving energy. This efficiency translates to significant cost savings on utility bills, making the B4 an economical option over its lifespan.

Moreover, the B4 employs a robust and durable construction. Engineered with top-quality materials, it boasts a glass-lined tank that prevents corrosion and extends the longevity of the unit. This durable design ensures that users can rely on their water heater for many years, thus reducing the frequency of replacements and repairs.

The Bradford-White B4 is equipped with state-of-the-art technologies to enhance user convenience. Among these technologies is the ICON System, which features an advanced gas control. This control system allows for precise temperature management and ensures optimal performance. Additionally, the B4 comes with a built-in diagnostic system that provides insight into the operation of the unit, helping users identify potential issues before they escalate.

Another significant characteristic of the B4 is its variety of sizes and configurations. This versatility allows for easy installation in different spaces, whether it be a compact utility room or a larger commercial setup. Available in various capacities, the B4 can efficiently deliver hot water for various needs, catering to families of different sizes or businesses with diverse requirements.

Safety is also a top priority for Bradford-White. The B4 includes safety features such as a temperature and pressure relief valve, which acts as a safeguard against potential malfunctions. This adds an extra layer of peace of mind for users concerned about operational safety.

In summary, the Bradford-White Corp B4 combines high efficiency, durable construction, advanced technologies, versatility, and safety features. This makes it more than just a water heater—it is a dependable solution for ensuring hot water availability for various applications. Whether for a home or a commercial setting, the B4 represents a commitment to quality and performance that users have come to trust.