Copper Brute B4 Volume Water Heaters Page 13
To
Drain
Heater
T1AB
Remote Temperature
Control for Heater
Heat Flow Pressure* Water Temp
Exch. Water Rate Drop Rise
Model Passes Category gpm L/s ft. m °F °C
175 2 Soft 22 1.4 5.8 1.8 13 7
Normal 34 2.1 11.2 3.4 8 4
Hard 46 2.9 19.1 5.8 6 3
4 Soft 11 0.7 4.9 1.5 25 14
Normal 17 1.1 9.3 2.8 16 9
Hard 23 1.5 15.9 4.8 12 7
250 2 Soft 22 1.4 5.8 1.8 18 10
Normal 34 2.1 11.2 3.4 12 7
Hard 46 2.9 19.1 5.8 9 5
4 Soft 11 0.7 4.9 1.5 35 19
Normal 17 1.1 9.3 2.8 33 18
Hard 23 1.5 15.9 4.8 17 9
325 2 Soft 34 2.1 12.5 3.8 18 10
Normal 34 2.1 12.5 3.8 18 10
Hard 46 2.9 21.7 6.6 11 6
4 Soft 17 0.7 10.4 3.2 36 20
Normal 17 0.7 10.4 3.2 30 17
Hard 23 1.5 18.1 5.5 22 12
400 2 Soft 34 2.1 13.3 4.1 19 11
Normal 34 2.1 13.3 4.1 19 11
Hard 46 2.9 23.4 7.1 14 8
4 Soft 17 0.7 11.1 3.4 37 21
Normal 17 0.7 11.1 3.4 37 21
Hard 23 1.5 19.5 5.9 27 15
*Pressure drop includes head loss of heat exchanger and through 30 feet (9.1 m) of pipe and normal  ttings when heater
is installed with storage tank. Pipe and ttings are assumed to be 1-1/2 inch (38 mm).
Main Circulating Loop
(With Own Pump)
Water Maintained
Less Than 110°F (43°C)
Adjustment Procedure
1. Turn on heater and open gate
valves A and B.
2. After 15 minutes, read T1.
3. If T1 is less than 110°F (43°C),
slowly close valve B until T1
climbs to 110°F (43°C).
4. If T1 is greater than 110°F (43°C),
slowly close valve A until T1
drops to 110°F (43°C).
5. Check after 5 minutes
operation and make nal
adjustments.
Figure 20. Cold water application.
Table 4. Pump Performance Requirements.