26
1. Circulators With space heating zones using circulators,
the Single-wall Indirect should be added as an additional
zone with a circulator.
2. Zone Valves Select a valve with a low-pressure drop
to assure adequate flow through the water heater.
3. Hybrid The space heating zone can be zoned using zone
valves and the Single-wall Indirect zoned with a circulator.
DOMESTIC HOT WATER PRIORITY
Two options are available, Priority and Non-Priority.
1. Priority Demand for space heating is interrupted or
postponed until the domestic hot water demand is
satisfied. This option provides maximum delivery of
domestic hot water. Priority is recommended when:
a) Boiler net output is 100,000 Btu per hour or less, or
b) When boiler output required to satisfy domestic hot
water demand is at least 50% of the boiler output
required to satisfy space heating demand, or
c) When an interruption in space heating can be
tolerated during a long domestic hot water draw.
2. Non-Priority Boiler output is divided between space
heating and domestic hot water heating. Delivery of
domestic hot water can be reduced during simultaneous
space and domestic hot water heating operations,
depending on such factors as boiler output, boiler over-
sizing, number of space heating zones calling for heat, and
the ratio of domestic hot water load to space heating load.
INTERNET VERSION FOR REFERENCE ONLY