SECTION VII: GAS CONNECTIONS

WARNING

Connect this water heater only to the type of gas as shown on the rating plate. Use clean black iron pipe or equivalent material approved by local codes and ordinances. (Dirt and scale from the pipe can enter the gas valve and cause it to malfunction). The inlet gas line must have at least a 3 inch (7.62 cm) drip leg (sediment trap) installed as close to the water heater’s gas valve as possible. A ground joint union must be installed in the gas supply line, as close to the water heater as possible, to permit servicing of the water heater. Compounds used on the threaded joints of the gas piping must be resistant to the action of liquefied petroleum gases/propane gas. DO NOT apply pipe dope to the gas valve inlet and make certain that no pipe dope has become lodged in the inlet screen of the gas valve. Extreme care must be taken to ensure no pipe dope enters the gas valve and to avoid excessive torque when tightening the gas supply line to the gas valve. Excessive torque may result in cracking of the gas valve housing. The suggested maximum torque is 31.5 foot lbs. (4.4 kg-m). The manufacturer of this water heater will not be liable for any damage or injury caused as a result of a cracked gas inlet as a result of excessive torque.

This water heater and its gas connection must be leak tested before placing the water heater in operation. Check for gas leaks with a soap and water solution and a brush or a commercial leak detector fluid.

NEVER USE A MATCH OR OPEN FLAME FOR TESTING!

The water heater is not intended for operation at higher than 10.5 inches water column, for natural gas,

13.5inches water column for L.P. supply gas pressure. Higher gas supply pressures require supplemental reducing service regulation. Exposure to higher gas supply pressure may cause damage to the gas controls, which could result in fire or explosion. If overpressure has occurred such as through improper testing of gas lines or emergency malfunction of the supply system, the gas valve must be checked for safe operation. Make sure that the outside vents on the supply regulators and the safety vent valves are protected against blockage. These are parts of the gas supply system, not the water heater.

WARNING

Conversion of this unit from natural gas to L.P. or L.P. to natural gas CANNOT be done in the field. If the gas supply does not match the type shown on the water heater rating plate, then contact your supplier for the proper water heater for the building gas supply.

CAUTION

The water heater and individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of ½ psi (3.5 kPa). The water heater must be isolated from the gas supply piping system by closing its manual shutoff valve during any pressure testing of the gas supply system at test pressures equal to or less than ½ psi (3.5 kPa). The supply line must be capped when not connected to the water heater.

If copper supply lines are used, they must be internally tinned and certified for gas service.

The gas supply lines must meet all requirements of the National Fuel Gas Code ANSI Z223.1 (Latest Edition), or in Canada CAN/CGA B149.1 Natural Gas Installation Code (Latest Edition) or CAN/CGA B149.2 Propane Installation Code (Latest Edition). The gas supply line may need to be larger for the EVERHOTwater heaters than a storage water heater in the case of a replacement installation. Refer to the piping capacity tables at the end of Section VII, “Gas Connections” and in the codes referenced above.

A 3” (7.6 cm) drip leg (sediment trap) is required ahead of the gas inlet connection to the water heater. See water heater installation illustration. Install a manual gas shutoff valve before the gas inlet connection to the water heater before connecting to the gas line. A union should be installed before the water heater gas connection for disconnection for servicing. Refer to the piping diagrams (Fig. 1-4) in Section V, “Water Connections”.

Check the type of gas and the gas inlet pressure before connecting the EVERHOT water heater to the gas supply. If the gas supply type does not match the type shown on the water heater rating plate, then DO NOT connect the water heater. Contact your Bradford White supplier for the correct water heater.

29

Page 29
Image 29
Bradford-White Corp IGI-180C, IGI-180R Section VII GAS Connections, Never USE a Match or Open Flame for Testing

IGI-180C, IGI-180R specifications

Bradford-White Corporation is a well-known name in the water heating industry, offering a range of reliable and efficient products. Among its noteworthy offerings are the IGI-180R and IGI-180C indirect water heaters. These models exemplify the company's commitment to quality and innovation, featuring robust designs and cutting-edge technologies.

The IGI-180R and IGI-180C units are designed to provide a consistent supply of hot water for residential and commercial applications. Both models have a storage capacity of 180 gallons, making them ideal for settings that require large volumes of hot water, such as restaurants, schools, and larger households. Their large tanks ensure minimal wait times and a reliable hot water supply, even during peak usage periods.

One of the key features of the IGI series is their indirect heating capability. Instead of relying on electric elements or gas burners, these heaters use a separate boiler or heating system to provide the necessary heat. This allows for more efficient operation, as the water is heated more evenly and effectively. The models integrate seamlessly with existing boiler systems, making them an excellent choice for those looking to upgrade or expand their hot water capabilities without extensive modifications.

Both the IGI-180R and IGI-180C incorporate advanced insulation technology, minimizing heat loss and improving energy efficiency. The high-density foam insulation encases the tank, keeping the water hot for longer periods and reducing energy costs associated with reheating. This insulation also contributes to a longer lifespan for the unit, as it reduces the wear and tear on the heating systems.

Another pivotal characteristic of these units is their durable construction. Bradford-White utilizes high-quality materials and rigorous manufacturing standards, ensuring that the IGI models withstand the test of time. The tanks are constructed from heavy-duty steel with a glass lining that protects against corrosion and sediment buildup, enhancing the longevity and performance of the water heater.

Lastly, both models come equipped with a range of safety features, including an integrated Pressure Relief Valve and a temperature control system. These elements safeguard against overheating and pressure issues, ensuring safe operation.

In conclusion, the IGI-180R and IGI-180C indirect water heaters by Bradford-White Corporation stand out for their efficient, reliable, and durable design. With advanced heating technology, excellent insulation, and robust safety features, they are a smart investment for any hot water demand scenario.