![](/images/new-backgrounds/1013819/1381911x1.webp)
6
INSTALLATION
Several issues must be addressed when selecting a suitable location for your
W3000 wood stove. Observing required clearances to combustible materials, the proximity to a safe chimney, and electrical supply (if optional blower in use) must all be considered. In addition, selecting a location that takes advantage of the building’s natural air flow is also desirable to maximize the heating effectiveness of the heater. In many cases, this is a central location within the building.
SPECIFICATIONS
FREESTANDING:
Width: 26”
Height: 29 ½”
Depth: 21 ¾” (total - from face)
Weight: 430 lbs.
Flue size: 6”
EPA status:
Burn time: 7 – 9 hours
BTU range: 9,500 to 37,000 BTU’s/hr
Approved installations:
FIREPLACE INSERT:
Width: 22 7/8” (at fireplace rear) 26” (at fireplace opening)
Height: 20” (in fireplace)
Depth: 21 ¼” (total – from face) 12 ¾” (in fireplace)
Flashing Size: 40 ½” W x 26 5/8” H (medium) 48 ½” W x 30 5/8” H (large)
Weight: 430 lbs.
Flashing: 13 lbs.
Flue size: 6”
EPA status:
Burn time: 7 – 9 hours
BTU range: 9,500 to 37,000 BTU’s/hr
Approved installations:
CLEARANCES
W3000FS
The stove must be placed on a continuous (grouted joints) noncombustible material such as ceramic tile, cement board, brick, 3/8” millboard or equivalent ½” material with a k+ .84 insulation factor, or other approved or listed material suited for floor protection. Check local codes for approved alternatives. Clearances for floor protection are measured from the sides, back, and face (door opening) as shown in figure 1.
Minimum clearance to combustibles must be maintained as shown in figure 2 and the following chart.
| A | B* | C | D* | E* | F | G | H |
Single Wall |
|
|
|
|
|
|
|
|
Connector | 24” | 14” | 16” | 14” | 7” | 16” | 84” | 30” |
Double Wall |
|
|
|
|
|
|
|
|
Connector | 22” | 12 ½” | 12” | 10” | 7” | 16” | 84” | 30” |
Alcove with |
|
|
|
|
|
|
|
|
Double Wall | 22” | 12 ½” | 12” | 10” | 7” | 16” | 84” | 30” |
Mobile Home |
|
|
|
|
|
|
|
|
Double Wall | 22” | 12 ½” | 12” | 10” | 7” | 16” | 84” | 30” |
*Given for reference only. Always maintain the clearances listed to the pipe.
W3000I
Minimum clearances to combustibles must be maintained as shown in figure 3 and the following chart. NOTE: Materials projecting more than ¾” from the wall are considered mantels.
| I | J | K | L | M | N | O | P |
W3000I | 24” | 32” | 18” | 9” | 19 15/16” | 4 9/16” | 8 ½” | 12 5/8” |
W3000I |
|
|
|
|
|
|
|
|
w/Heat Shield* | 16” | 24” | 18” | 9” | 19 15/16” | 4 9/16” | 8 ½” | 12 5/8” |
The floor in front of the stove must be protected as shown in figure 2 and as listed below. The floor protection must also extend 8” to either side of the door opening.
When hearth protection is a minimum of 2” high (Q), The depth (R) must be a minimum of 24”
When hearth protection is a minimum of 4” high (Q), The depth (R) must be a minimum of 21”
When hearth protection is a minimum of 6” high (Q), The depth (R) must be a minimum of 18”
When the stove is installed in factory built fireplaces, 2” of clearance must be maintained under the portion of the insert that extends out over the hearth extension.
DO NOT USE MAKESHIFT MATERIALS OR COMPROMISES IN THE INSTALLATION OF THIS UNIT.
INSTALL VENT WITH CLEARANCES SPECIFIED BY THE VENT MANUFACTURER.
FIGURE 1
FIGURE 2
*Use only the Breckwell Heat Shield – Part Number