Troubleshooting
Problem | Cause | Correction | |||
Automatic transfer switch does not | 1. | Generator breaker open. | 1. | Reset generator circuit breaker. | |
transfer to generator | 2. | Generator voltage not acceptable. | 2. | Refer to generator manual. | |
|
|
|
|
| |
Automatic transfer switch does not | 1. | Service disconnect breaker open. | 1. | Reset service disconnect breaker. | |
2. | Utility voltage not acceptable. | 2. | Wait for utility voltage to return to | ||
transfer to utility | |||||
|
|
| normal. | ||
|
|
|
| ||
|
|
| |||
Generator is still running after switch | Engine cool down period. | Engine should stop after 1 minute. | |||
transfers to utility power |
|
|
|
| |
|
|
|
|
| |
| 1. | 1. | Check | ||
|
| correctly. |
| proper operation and/or check | |
Generator or supervised loads (air |
|
|
| control wiring to external load. | |
2. | Too much load on generator. | 2. | Decrease load to generator. | ||
conditioner, etc.) are operating | |||||
improperly when generator is supplying | 3. | Current transformer not connected. | 3. | Plug CT connectors into control | |
power |
|
|
| module. | |
| 4. | Broken current transformer. | 4. | Contact local Briggs & Stratton | |
|
|
|
| service center. | |
|
|
|
|
| |
| 1. | Minimum engine run time has not | 1. | Wait five minutes for transfer | |
Generator is still running after utility |
| elapsed. |
| switch to retransfer to utility power. | |
power is restored | 2. | Fuse(s) in transfer switch is | 2. | Check fuse(s) and replace if | |
|
| defective. |
| necessary. | |
|
|
|
|
|
11