5250W Portable Generator

RECEPTACLES

CAUTION

Receptacles may be marked with rating value greater than generator output capacity.

NEVER attempt to power a device requiring more amperage than generator or receptacle can supply.

DO NOT overload the generator. See “Don’t Overload Generator”.

120/240 Volt AC, 30 Amp, Locking Receptacle

Use a NEMA L14–30 plug with this receptacle. Connect a 4–wire cord set rated for 250 Volt AC loads at 30 Amps (or greater) (Figure 5).You can use the same 4–wire cord if you plan to run a 120 Volt load.

This receptacle powers 120/240 Volt AC, 60 Hz, single phase loads requiring up to 5,250 watts of power

(5.25 kW) at 30 Amps for 120 Volts or 240 Volts.The outlet is protected by a push–to–reset circuit breaker.

120 Volt AC, 20 Amp, Duplex Receptacle

Each duplex receptacle (Figure 6) is protected against overload by a push–to–reset circuit breaker.

Figure 6 — 120 Volt, 20 Amp Duplex Receptacle

Figure 5 — 120/240 Volt AC, 30 Amp Receptacle

4-Wire Cord Set

240V

120V 120V

W (Neutral)

Y (Hot)

X (Hot)

NEMA L14-30

Ground (Green)

Use each receptacle to operate 120 Volt AC, single–phase, 60 Hz electrical loads requiring up to 2,400 watts (2.4 kW) at 20 Amps of current. Use cord sets that are rated for 125 Volt AC loads at 20 Amps (or greater).