OPERATION AND SPECIFICATIONS

9
SYSTEM OPERATION
To transfer from utility power to generator power:
1. Turn OFF main breaker labeled “UTILITY SUPPLY”.
2. Turn OFFall branch circuit breakers in transfer switch.
3. Slide mechanical interlock and turn “GENERATOR
SUPPLY” breaker to ON position.
4. Turn ON branch circuit breakers one at a time.
To transfer from generator power back to utility
power:
1. Turn OFFmain breaker labeled “GENERATOR
SUPPLY”.
2. Turn OFFall branch circuit breakers in transfer switch.
3. Slide mechanical interlock and turn “UTILITY SUPPLY”
breaker to ON position.
4. Turn ON branch circuit breakers one at a time.

Specifications

UL® 1008 Listed Transfer Switch
Model 071004
Enclosure. . . . . . . . . . . . . . . . . . . NEMA 1
Maximum Load/Circuit:
from Load Center . . . . . . . . . . 50 Amps
Rated AC Voltage. . . . . . . . . . . . . 250 Volts
Poles . . . . . . . . . . . . . . . . . . . . . . 2
Fault Current Rating. . . . . . . . . . 10,000 RMS Symmetrical
Amperes
Weight. . . . . . . . . . . . . . . . . . . . . 27 lbs.
Model 071005
Enclosure. . . . . . . . . . . . . . . . . . . NEMA 3R
Maximum Load/Circuit:
from Load Center . . . . . . . . . . 50 Amps
Rated AC Voltage. . . . . . . . . . . . . 250 Volts
Poles . . . . . . . . . . . . . . . . . . . . . . 2
Fault Current Rating. . . . . . . . . . 10,000 RMS Symmetrical
Amperes
Weight. . . . . . . . . . . . . . . . . . . . . 34 lbs.